What Is Switchgear, Types, Components, Ratings and How It Differs From a Transformer

Switchgear is a metal enclosed assembly that holds the breakers, switches and bus used to switch power, protect equipment and isolate sections of a system for maintenance. It can be rated up to 38 kV and up to 6000 amps. A transformer changes voltage and switchgear decides where the power goes and when it trips. Together with the transformer they make up the power equipment at the start of most commercial and industrial sites.

Updated November 20, 2026

The NEC definition and what it does

The National Electrical Code describes switchgear as an assembly completely enclosed on all sides and top with sheet metal, except for ventilating openings and inspection windows, containing primary power circuit switching, interrupting devices, or both, with buses and connections. It may include control and auxiliary devices, and access is through doors or removable covers. The jobs are protection from faults, isolation of sections for maintenance, and control of power flow.

What is inside

Circuit breakers interrupt fault current. Disconnect switches give a visible isolation point. Protective relays watch current and voltage and tell the breaker to trip. Current and potential transformers feed the relays and meters, control power transformers supply the control voltage, and busbars carry the power between them. In switchgear each breaker sits in its own compartment.

Low voltage, medium voltage and the standards

Low voltage switchgear is built to UL 1558 and typically serves 600 V class systems with draw out power breakers. Medium voltage switchgear runs from the 5 kV class through 38 kV. IEEE C37.20.2 is the standard cited for metal clad construction, built from factory assembled cubicles, and metal enclosed medium voltage gear can be built around load interrupter switches and fuses instead of draw out breakers.

Voltage classTypical useImpulse withstand (BIL)
4.76 kV classLarge motor control and plant distribution60 kV peak, one maker published rating
15 kV classUtility service entrance, campus and data center distribution95 kV peak
38 kV classLarge industrial campuses and utility interfaces170 kV peak
600 V classBuilding and industrial low voltage mainsNot applicable, UL 1558 gear

BIL figures are one manufacturer catalog set, check the nameplate or datasheet of the actual lineup.

Draw out breakers and short circuit rating

Switchgear normally uses draw out breakers that can be detached from the bus and removed for maintenance without shutting down the main or affecting other breakers. A breaker with moving parts needs regular maintenance, and working with it energized needs arc flash protective equipment. Because each breaker has its own compartment, switchgear is rated to withstand a short circuit for up to 30 cycles, while panelboards and switchboards are rated for 3 cycles. Product examples from one maker show interrupting ratings up to 63 kA for 5 and 15 kV class metal clad switchgear and up to 40 kA at 38 kV.

Arc resistant switchgear

Arc resistant designs are built and tested to contain and vent an internal arcing fault away from people. IEEE C37.20.7 is the guide for testing switchgear for internal arcing faults, and arc resistant lineups are marked with accessibility types such as Type 2B. Remote racking of breakers is an additional way to keep operators out of the arc flash boundary.

Switchgear, transformer and substation

A transformer converts voltage, a pad mounted transformer drops utility distribution voltage to 480Y/277 or 208Y/120 for a building. Switchgear sits on either side, with medium voltage switchgear ahead of the transformer on the primary and low voltage switchgear or a switchboard after it on the secondary. A substation is the full yard of transformers, switchgear, breakers and controls. Main service switchgear is often installed outdoors, and a section can hold the utility metering current transformers.

Cost, lead time and used switchgear

A switchgear line up that cost six figures new rarely scraps for its metal. One Arizona fabricator quotes 2026 factory lead times of 16 to 26 weeks for 1600 to 4000 A low voltage switchgear and 20 to 36 weeks for 5 kV class metal clad gear. A used equipment dealer says 16 to 20 weeks is common for new switchgear, which is pushing used prices up. When buying used, confirm the ratings, configuration, breaker frame, trip unit and interlocks against the application, ask what cleaning and testing was done, and ask for nameplate photos, serial numbers and test records. A complete line up with its breakers is worth more than parted out gear.

Related pages

Common questions

What is switchgear in simple terms

An enclosed assembly of breakers, switches, relays and bus that switches power, protects equipment from faults and isolates sections for maintenance.

What is the difference between switchgear and a transformer

A transformer changes voltage. Switchgear connects, protects and disconnects circuits without changing the voltage.

What is the difference between switchgear and a switchboard

Switchgear normally has draw out breakers in separate compartments and a 30 cycle short circuit rating. A switchboard is rated for 3 cycles and often uses bolt on breakers. See our full comparison.

What voltages does switchgear cover

From low voltage 600 V class up to 38 kV, with current ratings up to 6000 A.

What is metal clad switchgear

A factory assembled cubicle construction for medium voltage switchgear with draw out breakers. IEEE C37.20.2 is the standard cited for it.

What is arc resistant switchgear

Switchgear tested under IEEE C37.20.7 to withstand and direct an internal arcing fault away from the operator.