Solar and BESS collector substations, what is in the package, published costs and lead items
A collector substation gathers the 34.5 kV feeders from a solar or battery plant and steps the power up to the grid voltage through a main power transformer. The package also holds breakers, switchgear, protection and a control house. Buyers either hire an EPC for the whole package or buy the major equipment themselves, and we help with the second path.
Updated November 15, 2026
What is in a collector substation
Three public projects show the range. Burns and McDonnell describes an 80 MW solar plant in West Virginia with a 138/34.5 kV substation holding four underground feeders, one power transformer, a 138 kV circuit breaker and a prefabricated metal clad switchgear and control enclosure on a skid. Its 138 kV switchyard has three 145 kV breakers, six disconnect switches and a prefabricated control building.
Kiewit describes a 34.5/138 kV collector substation at a 734 acre solar site, with two transformers, a medium voltage collector system of two rigid buses with provisions for incoming underground feeders, two capacitor banks and a prefabricated control house. A study of a 450 MWac plant used a single 300/400/500 MVA transformer, a 345 kV breaker and a half diameter, and two 38 kV metal clad lineups rated 40 kA for 3 seconds with ten feeder breakers each, 20 feeders in all.
Feeder current at 34.5 kV
Collector feeders are sized by the megawatts they carry. The 450 MWac study set a design maximum of 23.0 MW per feeder, which it gives as 385 A at the substation. The table is computed at unity power factor from MW divided by the square root of 3 times 34.5 kV, and the same method gives the main breaker and bus current for the whole plant.
| Plant or feeder output | Current at 34.5 kV |
|---|---|
| 5 MW | 84 A |
| 10 MW | 167 A |
| 15 MW | 251 A |
| 20 MW | 335 A |
| 23 MW | 385 A |
| 50 MW | 837 A |
| 80 MW | 1,339 A |
| 100 MW | 1,673 A |
Computed values rounded to the nearest amp. Real designs add power factor, derating and margin.
Cost examples
We found no single public price list for a collector substation, so use these as context. Electrical Trader gives published ranges for complete substations of $3M to $8M for a medium distribution substation of 20 to 50 MVA and $8M to $30M for transmission class of 100 to 300 MVA, and puts power transformers alone at $250,000 to over $7M. It says civil works and installation run 40 to 60 percent of equipment cost. NextMSC gives $15,000 to $21,000 per MVA for the main transformer alone. We publish no prices of our own.
The 450 MWac study also shows where the money goes outside the substation. It put about 190 km of 35 kV cable in the collector network and reported that re optimizing the collector cut modelled losses from 2.9 percent to 1.8 percent of annual energy, about 12,800 MWh a year, while trimming installed cable cost by about 8 percent.
Long lead items and timeline
The main power transformer sets the schedule. The 450 MWac study used a 62 week lead time for it, and Wood Mackenzie reports about 128 weeks for power transformers on average in the second quarter of 2025. High voltage breakers, load tap changers and bushings can also run long, so order them early. Prefabricated control houses and switchgear skids shorten the field schedule, and Burns and McDonnell used them on the West Virginia project.
Giga lists medium voltage substation transformers up to 35 kV and 60 MVA with made to order times as fast as 26 weeks, which is the maker claim for its own lines.
What we can source
We quote the main power transformer, the inverter block pad mounts and medium voltage switchgear. Send the one line diagram, the voltage classes and the date you need power, and say whether you want individual equipment or the whole package priced.
What to send for a quote
- One line diagram or the main equipment list
- Plant output in MWac and the interconnection voltage
- Collector voltage and number of feeders
- Main transformer MVA ratings, impedance and tap range
- Breaker, switchgear and protection requirements from the utility
- Package or individual equipment, and the energization date
- Site location
Common questions
What is a collector substation
It is the substation that gathers the medium voltage feeders from a solar or storage plant and steps the power up to the grid voltage.
What is in a solar collector substation
A main power transformer, breakers and disconnects, medium voltage switchgear, protection and controls in a control house, and often capacitor banks.
How much does a collector substation cost
No single public price exists. Electrical Trader gives $3M to $8M for a 20 to 50 MVA distribution substation and $8M to $30M for 100 to 300 MVA transmission class.
How long does a collector substation take
The main transformer drives it. Wood Mackenzie reports about 128 weeks for power transformers on average, and one public study used 62 weeks.
What current does a 34.5 kV feeder carry
A 20 MW feeder at unity power factor carries about 335 A. One public study set a maximum of 23 MW or 385 A per feeder.
Related pages
Sources
- Burns and McDonnell, Solar interconnection substation and switchyard
- Kiewit, Copperhead solar substation and interconnect
- Keentel Engineering, Utility scale solar collector study
- Electrical Trader, Substations, new and used equipment and costs
- NextMSC, US transformer and switchgear prices, lead times and supply constraints 2026, October 2026 update
- Wood Mackenzie, Supply shortages and an inflexible market give rise to high power transformer lead times
- EEPower, Transformer supply chain woes persist as energy demand grows (Wood Mackenzie lead times)
- Giga Energy, Medium voltage substations
Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.