Natural gas generators, 100 kW to 2 MW commercial sets

A natural gas generator runs from the gas line, so there is no fuel tank to fill and no diesel to turn over. Below are the commercial models we found from 100 kW to 2 MW, the gas burn the makers publish, the current each size delivers at 480 volts, and the questions about gas supply that decide whether a gas set will work on your site. We source new, surplus and used gas sets and quote them delivered.

Updated November 21, 2026

Natural gas generator models by size

These are the published ratings for the models we found. Ratings change with voltage, duty and emissions package, so confirm them on the spec sheet for the exact model you are quoted. A set rated standby is not rated for continuous prime duty at the same kW.

SizeMaker and modelPublished rating
100 kWCummins C100N6100 kW natural gas
100 kWCummins GGHH100 kW natural gas
100 kWGenerac SG100100 kW industrial gaseous
100 kWGlobal Power HNI 100100 kW natural gas
150 kWGenerac MG150150 kW industrial gaseous
200 kWCaterpillar DG200 GC200 kW natural gas
500 kWCummins C500N6B500 kW (625 kVA) standby, GTA28E engine
500 kWGenerac SG500500 kW (625 kVA) standby, 450 kW prime, 25.8 liter engine
500 kWCaterpillar DG500500 ekW, Cat CG18 engine
1,000 kWCummins C1000N6B1,000 kW (1,250 kVA) standby, QSK60G engine
1,000 kWCaterpillar G35121,000 kW on Cat's 60 Hz natural gas range
1,500 kWCaterpillar G35161,500 ekW at 0.8 power factor, 1,800 rpm, 40,384 lb set
2,000 kWCaterpillar G35202,000 kW on Cat's 60 Hz natural gas range

From the maker and dealer pages listed under sources, read November 2026. Cummins lists the C1000N6C as a lean burn variant on the same QSK60G family with a continuous 1,000 kW (1,250 kVA) rating.

How much gas a natural gas generator burns

Makers publish gas burn in cubic feet an hour at quarter, half, three quarter and full load. The sheets below are for 100 kW and 200 kW sets. Gas burn per kilowatt falls a little as load rises, so a set that runs near full load is cheaper per kWh than one that idles.

The last column is computed from the sheet, full load cubic feet an hour divided by the kW rating. It lands between about 11.8 and 13.2 cubic feet per kWh for these sets.

Model25 percent load50 percent load75 percent load100 percent loadCubic feet per kWh at full load
Cummins C100N6, 100 kW549.6 scfh805.4 scfh1,050.8 scfh1,317.7 scfh13.2
Cummins GGHH, 100 kW433.2 cu ft/hr666.4 cu ft/hr914.0 cu ft/hr1,175.8 cu ft/hr11.8
Global Power HNI 100, 100 kW328 cu ft/hrnot stated in our sourcenot stated in our source1,247 cu ft/hr12.5
Caterpillar DG200 GC, 200 kW900 cu ft/hrnot stated in our sourcenot stated in our source2,571 cu ft/hr12.9

From the spec and submittal sheets listed under sources. Sheets assume different gas heating values, so compare sets on the same basis. Powergen puts a gas set at about 10,000 BTU per kWh at 75 percent load, which is about 10 cubic feet of gas per kWh at roughly 1,000 BTU per cubic foot.

Full load amps by size

Gas sets are rated in kW at a power factor of 0.8, so kVA is kW divided by 0.8. The current is computed from that. Use it to size the transfer switch, the main breaker and the cable.

Set sizekVA at 0.8 power factorAmps at 208 VAmps at 480 VAmps at 600 V
100 kW125347150120
200 kW250694301241
500 kW6251,735752601
1,000 kW1,2503,4701,5041,203
1,500 kW1,8755,2042,2551,804
2,000 kW2,5006,9393,0072,406

Computed. Amps equal kVA times 1,000 divided by the square root of 3 times the voltage, three phase.

Natural gas or diesel

Generator Source describes a natural gas set as running from the gas line with no tank to refill, which suits long running or prime power where the supply is strong. A diesel set stores its fuel on site and is still the usual choice for emergency backup because the fuel is on hand during a gas outage.

On fuel cost per kWh, Powergen estimates about $0.12 for natural gas against $0.30 to $0.37 for diesel. Those figures rest on Powergen's own assumed prices of $1.20 a therm and $4.50 to $5.50 a gallon, so run them again with your local rates. For scale, a 500 kW diesel set burns roughly 33 to 37 gallons an hour at full load.

What to confirm about the gas supply before you buy

A gas set is only as good as the gas behind it. None of the sheets we read give one number that fits every site, so ask the maker for the inlet pressure and flow at your load, and ask the gas utility whether the service can deliver it.

A 2,000 kW set can call for more than 25,000 cubic feet an hour if it burns what the 200 kW sheet above implies per kWh, which is a service line and a meter the utility has to size. That is a computed estimate, not a published figure. Also confirm that the set can start and carry load when the gas pressure drops during a widespread outage.

Used and surplus natural gas sets

Used and surplus gas sets are sold. Ask for the hours, the last overhaul, a load bank test and the emissions certification, because the emissions system matters as much as the engine. See our guide to used generators for the checks to demand. We did not find a public price list for gas sets that we trust, so we do not print one. Send the size and voltage and we quote new, surplus and used sets and say which is which.

What to send for a quote

  • Size in kW or kVA and voltage, for example 480Y/277
  • Standby, prime or continuous rating
  • Gas pressure and flow available at the site, or the gas utility contact
  • Emissions requirement from your air permit
  • Enclosure, open, weather or sound attenuated
  • New, surplus or used, and the hours you will accept
  • Transfer switch, paralleling gear or step up transformer needed
  • Site ZIP code and the date you need power

Common questions

How much gas does a commercial natural gas generator use

Published sheets give about 1,176 to 1,318 cubic feet an hour at full load for a 100 kW set and 2,571 cubic feet an hour for a Cat DG200 GC at 200 kW. That is roughly 12 to 13 cubic feet per kWh.

How many amps does a 500 kW natural gas generator produce

A 500 kW set is 625 kVA at 0.8 power factor, which is 752 A at 480 V and 1,735 A at 208 V, three phase.

What sizes do commercial natural gas generators come in

Makers list sets from 100 kW up to 2,000 kW and beyond. The Cat gas range runs G3512 at 1,000 kW, G3516 at 1,500 kW and G3520 at 2,000 kW, and Cummins lists 1,000 kW QSK60G sets.

Is a natural gas generator cheaper to run than diesel

Powergen estimates about $0.12 per kWh for natural gas against $0.30 to $0.37 for diesel, using its own assumed fuel prices. Check the result against your local gas and diesel rates.

Can a natural gas generator be used for emergency standby

Yes, many are sold for standby. The difference is that the fuel comes from the gas line, so confirm the supply stays up in an outage and size the service for the load.

Do you sell used natural gas generators

We source new, surplus and used gas sets. Send the size, voltage and duty and we quote what is available, with the hours and test history stated.