A 100 kW generator set is 125 kVA at the usual 0.8 power factor and delivers about 150 amps at 480 volts three phase. It is the standby size for a small clinic, a school wing, a telecom site or a workshop. Below are the 100 kW models we found, the amps at each voltage, the public listing prices we read, and the transfer switch that goes with one. We source new, surplus and used 100 kW sets and quote them delivered.

Updated November 21, 2026

100 kW and 125 kVA are the same set

Generator sets are sold in kW at a power factor of 0.8, so a 100 kW set is a 125 kVA set. One 100 kW and 125 kVA spec sheet lists 151 amps at 480 volts three phase. A listing for a 100 kVA generator is a smaller unit, 80 kW.

Check whether a price is for the standby or the prime rating. The same engine carries a lower kW figure for prime power.

Voltage, three phaseFull load amps at 125 kVA
208 V347
240 V301
480 V150
600 V120

Computed. Amps equal kVA times 1,000 divided by the square root of 3 times the voltage. Single phase sets use a different formula, so send the voltage and phase.

100 kW models and listings we found

These are the 100 kW sets that came up in maker pages and dealer and surplus listings read in November 2026. Ratings change with voltage, emissions package and duty, so confirm them on the sheet for the exact unit.

UnitFuelDetails from the listing or sheet
Cummins C100D2REDiesel100 kW, trailer mounted, Tier 4 Final, surplus listing
Generac SD100Diesel120/240 V single phase, 152 hp Iveco FPT 6.7 liter engine, Tier 3, sound enclosure, 350 gallon sub base tank, 261 hours
Caterpillar XQ125Diesel100 kW mobile set, Tier 4 Final, 480 V, 2018, listings at 7,112 and 8,289 hours
Multiquip DCA125Diesel100 kW, 480 V, 2019, 11,893 hours
Blue Star Power PD100Diesel100 kW, 480 V, Tier 3, 2020
Cummins Onan DSGAADiesel100 kW, 277/480 V, QSB7 G3 engine, skid mounted with circuit breaker, 2009
Kohler 100ROZJ71Diesel100 kW, 480 V, 1998, 805 hours
Cummins C100N6Natural gas100 kW, full load gas burn 1,317.7 scfh on the submittal
Cummins GGHHNatural gas100 kW, full load gas burn 1,175.8 cubic feet an hour on the sheet
Generac SG100Natural gas100 kW industrial gaseous set

From the listings and sheets under sources. Surplus listings are single units that may be sold.

100 kW generator prices

These are public listing figures, not our prices. Enclosure, controls, emissions package, voltage and whether a transfer switch comes with the set move the price as much as the brand. We did not find a published list price for Cat, Cummins or Kohler 100 kW sets, so none is printed.

UnitListing figureSource
New Perkins powered 100 kW 125 kVA diesel set$37,662.50Dealer listing, read November 2026
New Cummins 125 kW industrial set, 277/480 V three phase$45,862.99Dealer listing, read November 2026 (125 kW, not 100 kW)
Used 1998 Kohler 100ROZJ71, 805 hours$9,950 askingSurplus Record listing, read November 2026

Asking prices are not sold prices. Installation, the transfer switch, permitting, fuel and freight are extra. For the same question at 500 kW with Depco and PowerGen ranges, see the 500 kW page.

Diesel or natural gas at 100 kW

A diesel set stores its fuel on site, so it keeps running through a gas outage. A natural gas set runs from the gas line and has no tank to refill, according to Generator Source. At full load the Cummins GGHH sheet shows 1,175.8 cubic feet of gas an hour and the C100N6 submittal 1,317.7, so ask the gas utility whether the service can deliver that before you choose gas.

The gear that goes with a 100 kW set

At 480 V the set puts out about 150 A, so the transfer switch, the main breaker and the cable all have to be rated above that. A 100 kW set is within the smallest frame of the ASCO 300 series, which ASCO publishes from 30 A to 230 A. Generator duty drives the emissions tier too, so tell us whether the set is for emergency use only. We quote the set and the transfer switch on one delivered quote so the ratings line up before anything ships.

What to send for a quote

  • Standby, prime or continuous rating, and kW or kVA
  • Voltage and phase, for example 277/480 V three phase or 120/240 V single phase
  • Diesel or natural gas
  • Emergency only or non emergency duty, and the emissions tier you need
  • Enclosure, open, weather or sound attenuated, trailer or skid, and runtime wanted from the tank
  • New, surplus or used, and the hours you will accept
  • Transfer switch needed, and its amp rating
  • Site ZIP code and the date you need power

Common questions

How much does a 100 kW generator cost

Listings we read in November 2026 ranged from $9,950 for a used 1998 Kohler to $37,662.50 for a new Perkins powered 100 kW set. We found no published list price for new Cat, Cummins or Kohler 100 kW sets.

How many amps is a 100 kW generator

At 0.8 power factor a 100 kW set is 125 kVA, which is 150 A at 480 V, 347 A at 208 V and 120 A at 600 V, three phase.

Is a 125 kVA generator the same as 100 kW

Yes. Generator sets are rated at 0.8 power factor, so 125 kVA times 0.8 is 100 kW.

What size transfer switch goes with a 100 kW generator

One rated above 150 A at 480 V. In the ASCO 300 series that is the D frame, which ASCO publishes from 30 A to 230 A.

Can I buy a used 100 kW generator

Yes. Surplus listings show 100 kW sets from 2009 to 2020 with 261 to more than 11,000 hours. Ask for a load bank test and the hours.

Is there a 100 kW natural gas generator

Yes. Cummins lists the C100N6 and the GGHH, and Generac lists the SG100, all at 100 kW.

Related pages

Sources

Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.

CallGet a quote