Home / Tools / Generator fuel consumption calculator and chart
Generator fuel consumption calculator and chart
How much fuel a generator burns depends on its size and how hard it is working. Pick the fuel, enter the size and load, and get fuel per hour, fuel for the run and the cost per hour and per kWh. The charts below give diesel use from 20 to 2,250 kW at four loads, natural gas and propane figures and tank sizes for 24, 48 and 72 hours.
Updated November 17, 2026
Diesel results are interpolated in the chart below. Starting prices in the form are examples, not market prices.
Diesel fuel consumption chart, 20 to 2,250 kW
Gallons an hour at quarter, half, three quarter and full load, with liters an hour at full load. These are approximate figures that two generator dealers publish as the same table. Engine make, model, age and load all move the real number, so the data sheet for a specific engine always wins.
| Generator kW | 25% load gal/hr | 50% load gal/hr | 75% load gal/hr | 100% load gal/hr | 100% load liters/hr |
|---|---|---|---|---|---|
| 20 | 0.6 | 0.9 | 1.3 | 1.6 | 6.1 |
| 30 | 1.3 | 1.8 | 2.4 | 2.9 | 11.0 |
| 40 | 1.6 | 2.3 | 3.2 | 4.0 | 15.1 |
| 60 | 1.8 | 2.9 | 3.8 | 4.8 | 18.2 |
| 75 | 2.4 | 3.4 | 4.6 | 6.1 | 23.1 |
| 100 | 2.6 | 4.1 | 5.8 | 7.4 | 28.0 |
| 125 | 3.1 | 5.0 | 7.1 | 9.1 | 34.4 |
| 135 | 3.3 | 5.4 | 7.6 | 9.8 | 37.1 |
| 150 | 3.6 | 5.9 | 8.4 | 10.9 | 41.3 |
| 175 | 4.1 | 6.8 | 9.7 | 12.7 | 48.1 |
| 200 | 4.7 | 7.7 | 11.0 | 14.4 | 54.5 |
| 230 | 5.3 | 8.8 | 12.5 | 16.6 | 62.8 |
| 250 | 5.7 | 9.5 | 13.6 | 18.0 | 68.1 |
| 300 | 6.8 | 11.3 | 16.1 | 21.5 | 81.4 |
| 350 | 7.9 | 13.1 | 18.7 | 25.1 | 95.0 |
| 400 | 8.9 | 14.9 | 21.3 | 28.6 | 108.3 |
| 500 | 11.0 | 18.5 | 26.4 | 35.7 | 135.1 |
| 600 | 13.2 | 22.0 | 31.5 | 42.8 | 162.0 |
| 750 | 16.3 | 27.4 | 39.3 | 53.4 | 202.1 |
| 1,000 | 21.6 | 36.4 | 52.1 | 71.1 | 269.1 |
| 1,250 | 26.9 | 45.3 | 65.0 | 88.8 | 336.1 |
| 1,500 | 32.2 | 54.3 | 77.8 | 106.5 | 403.1 |
| 1,750 | 37.5 | 63.2 | 90.7 | 124.2 | 470.1 |
| 2,000 | 42.8 | 72.2 | 103.5 | 141.9 | 537.1 |
| 2,250 | 48.1 | 81.1 | 116.4 | 159.6 | 604.2 |
Free to cite with a link to this page. Source table from Worldwide Power Products and Depco, liters computed at 3.785 per gallon.
Fuel use is not linear with load
An engine burns a fixed amount just to turn over and run its own auxiliaries, so fuel per hour does not fall in step with the load. In the chart a 500 kW set burns 11.0 gallons an hour at quarter load, which is 31 percent of the full load 35.7 for a quarter of the output. Fuel per kWh is therefore best at three quarter to full load and worst at light load. A set that spends its life at 20 percent load is oversized, burns more per kWh than it needs to and is harder on the engine, which is also why NFPA 110 asks for a minimum load of 30 percent on regular exercise runs. See the load bank testing guide.
Diesel tank size for 24, 48 and 72 hours
Gallons burned at three quarter load, and at full load in brackets, computed from the chart. Real tanks are not run to empty, so the tank holds more than the figure.
| Generator kW | Gal/hr at 75% | 24 hours | 48 hours | 72 hours |
|---|---|---|---|---|
| 100 | 5.8 | 139 (178) | 278 (355) | 418 (533) |
| 250 | 13.6 | 326 (432) | 653 (864) | 979 (1,296) |
| 500 | 26.4 | 634 (857) | 1,267 (1,714) | 1,901 (2,570) |
| 1,000 | 52.1 | 1,250 (1,706) | 2,501 (3,413) | 3,751 (5,119) |
| 2,000 | 103.5 | 2,484 (3,406) | 4,968 (6,811) | 7,452 (10,217) |
Natural gas and propane figures
Published figures are mostly for home standby sets. Three listings for 22 kW units give the range below. Ratings differ by model, so treat these as examples of the size of the number, not a table for every set.
| 22 kW model | Natural gas, half load cu ft/hr | Natural gas, full load cu ft/hr | Propane, half load gal/hr | Propane, full load gal/hr |
|---|---|---|---|---|
| Generac RG02224 | 190 | 316 | 2.1 | 3.4 |
| Generac 7042 Guardian | 203 | 306 | 2.53 | 3.9 |
| Generac 7260 | 221 | 311 | 2.0 | 4.0 |
The calculator scales the RG02224 figures by kW, which is 14.4 cubic feet of gas or 0.155 gallon of propane per kWh at full load. Energy content turns those into a rough efficiency check. A gallon of diesel holds 137,381 Btu, a gallon of propane 91,452 Btu and a cubic foot of natural gas 1,036 Btu. At full load the 200 kW diesel set in the chart uses 14.4 gallons an hour, which is about 1.98 million Btu for 682,000 Btu of electric output, roughly 35 percent. The 22 kW gas set burns 316 cubic feet, about 327,000 Btu for 75,000 Btu of output, roughly 23 percent. Small spark ignited sets convert less of the fuel than a large diesel.
Fuel cost per kWh
Cost per kWh is gallons an hour times the price divided by the kW delivered. A 100 kW diesel set at full load burns 7.4 gallons an hour, so at a fuel price of $4 a gallon that is $29.60 an hour or $0.296 per kWh. At half load it burns 4.1 gallons for 50 kW, $16.40 an hour or $0.328 per kWh. Fuel is only part of the cost of running a set. Maintenance, testing and the generator itself come on top, which is why a diesel set can look expensive per kWh against grid power.
Related
Size the set first with the generator kVA to kW and amps chart and the kVA to kW calculator. See 500 kW generators, 1 MW generators and used generators, or request a quote for a generator. For temporary power see mobile substations and temporary power.
Common questions
How much fuel does a diesel generator use per hour
A 100 kW diesel set burns about 7.4 gallons an hour at full load, 5.8 at three quarter load, 4.1 at half load and 2.6 at quarter load. A 500 kW set burns about 35.7 gallons an hour at full load and 18.5 at half load. The chart on this page lists 25 sizes from 20 to 2,250 kW.
How do you calculate generator fuel consumption
Read gallons per hour for the generator size and load from the engine data sheet or the chart, then multiply by the hours of run time. Fuel cost per kWh is the gallons per hour times the price per gallon divided by the kW the set is delivering. A 500 kW set at half load burns 18.5 gallons an hour for 250 kW, so at $4 a gallon the fuel is $74 an hour or about $0.30 per kWh.
Does a generator burn less fuel at half load
Yes, but not half as much. The 500 kW set burns 18.5 gallons an hour at half load against 35.7 at full load, which is 52 percent of the fuel for 50 percent of the output. At quarter load it still burns 11.0 gallons an hour, 31 percent of the full load figure for 25 percent of the output. Fuel per kWh is best near three quarter to full load.
How big a fuel tank do I need for 24, 48 or 72 hours
Multiply gallons per hour at your expected load by the hours. A 500 kW diesel set at three quarter load burns 26.4 gallons an hour, so 24 hours is 634 gallons, 48 hours is 1,267 and 72 hours is 1,901. Tanks are not run to empty and codes and the engine maker set the usable share, so size above the raw figure.
How much natural gas does a generator use
For the Generac 22 kW RG02224 home standby set, 190 cubic feet an hour at half load and 316 at full load. Other 22 kW units on the same fuel are listed between 203 and 221 cubic feet at half load and 306 to 316 at full load. Larger gas sets use more in total but less per kWh, so use the engine data sheet for a commercial unit.
Why do charts from different sites disagree
They are estimates, not measurements. The diesel table here is the one Worldwide Power Products and Depco both publish and it notes that real use depends on engine make, model, age and load. A rule of thumb of about 0.1 gallon per kWh gives 10 gallons an hour for 100 kW, above the 7.4 in the chart, so check the data sheet for the exact engine.
Sources
- Worldwide Power Products, Approximate Diesel Fuel Consumption Chart, https://www.wpowerproducts.com/power-generation-resources/diesel-fuel-consumption-chart/ (same table at https://www.depco.com/resources/diesel-fuel-consumption-chart/)
- Generac support, How Much Fuel Does My Home Standby Generator Use, the 22 kW RG02224 natural gas and propane figures, https://support.generac.com/articles/Knowledge/How-Much-Fuel-Does-My-Home-Standby-Generator-Use
- Supply House listing for the Generac 7042 Guardian 22 kW and Ferguson listing for the Generac 7260 22 kW, natural gas and LP figures at half and full load
- U.S. Energy Information Administration Btu conversion table, 137,381 Btu per gallon of diesel, 91,452 Btu per gallon of propane and 1,036 Btu per cubic foot of natural gas, https://www.eia.gov/energyexplained/units-and-calculators/british-thermal-units.php
- Every other number on this page is computed from those tables. Conversions use 3.785 liters per US gallon. The prices in the calculator are starting examples only, enter your own.