How Much Power Does a Hospital Use

An average US inpatient hospital used about 193.3 thousand Btu per square foot in the 2018 federal commercial buildings survey. That is about 56.6 kWh of total energy per square foot a year, counting gas and steam as well as electricity. A 500,000 square foot hospital therefore uses energy equal to an average of about 3.2 MW around the clock. This guide turns the survey figure into numbers you can plan with.

Updated November 18, 2026

The number to start from

The US Energy Information Administration 2018 Commercial Buildings Energy Consumption Survey puts inpatient health care buildings at 193.3 thousand Btu per square foot of total energy a year, and outpatient health care buildings at 82.0. Space heating is the largest single use in inpatient buildings at 62.6 thousand Btu per square foot. The figure is total site energy from all fuels, so it overstates electricity alone. Treat it as an upper bound for the electric load and use your utility bills for the real split.

Annual energy and average load for inpatient hospitals

Each row multiplies floor area by 193.3 thousand Btu and converts at 3,412 Btu per kWh. Average kW is annual kWh equivalent divided by 8,760 hours. The result is an average of all energy, not a peak demand and not an electric service size.

Floor area sq ftAnnual energy MMBtuAnnual energy million kWh equivalentAverage kW equivalent
100,00019,3305.70.6
250,00048,32514.21.6
500,00096,65028.33.2
1,000,000193,30056.76.5

Computed from the EIA 2018 CBECS inpatient figure of 193.3 thousand Btu per square foot. Real buildings vary widely by climate, age and services.

Outpatient health care buildings

Outpatient buildings use far less, 82.0 thousand Btu per square foot in the same survey, about 24 kWh equivalent per square foot a year.

Floor area sq ftAnnual energy MMBtuAnnual energy million kWh equivalentAverage kW equivalent
10,0008200.240.03
50,0004,1001.200.14
100,0008,2002.400.27

Computed from the EIA 2018 CBECS outpatient figure of 82.0 thousand Btu per square foot.

Average load is not the service size

A utility sizes the service and its transformers for peak demand, which sits above the average, and a hospital also needs capacity for standby generation and spare capacity for growth. This page does not publish a peak per square foot because no source read for it gives one. Take peak kW from the facility load study or the last twelve months of utility demand bills, then size the transformer with the transformer sizing calculator and the generator with the generator kVA, kW and amps chart.

What happens in an outage

Hospitals run on utility power with on site generators and automatic transfer switches that pick up the life safety and critical loads when the utility fails. Larger sites often add a second utility feed. The generator and transfer switch ratings come from the emergency load list, not from the annual energy figure, so use the numbers above for budgeting and the load list for equipment.

Transformers at a hospital

Medical campuses typically take medium voltage from the utility and step it down on site with pad mounted or indoor transformers to 480Y/277 or 208Y/120. Loads such as imaging, chillers and surgical suites are fed from separate branches. To convert any load in kW to current see the kVA to amps calculator, and for the other direction the kW to amps calculator.

Related pages

Common questions

How much electricity does a hospital use a year

The federal survey gives total energy, not electricity alone. An inpatient hospital averages 193.3 thousand Btu per square foot a year across all fuels, about 56.6 kWh equivalent. A 500,000 square foot hospital is about 28.3 million kWh equivalent a year. Electricity is only part of that, so read your own utility bills.

How much power does a hospital use per square foot

About 193.3 thousand Btu per square foot a year for inpatient buildings and 82.0 for outpatient buildings, from the EIA 2018 survey. In kWh equivalent that is about 56.6 and 24.0.

How many megawatts does a hospital use

On average, a 500,000 square foot inpatient hospital uses energy equal to about 3.2 MW around the clock, computed from the survey figure. The electric peak is a different number and comes from the facility load study.

What is the largest energy use in a hospital

In the EIA survey, space heating is the largest single use in inpatient buildings at 62.6 thousand Btu per square foot, about a third of the total.

What size generator does a hospital need

It depends on the emergency load list, which is set by code and by the hospital. No fixed ratio per bed or per square foot is published here because none was found in a source read for this guide. Use the load list and see the generator kVA, kW and amps chart.

Sources

Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.