Home / Charts / Generator kVA to kW and amps chart
Generator kVA to kW and amps chart
Generators are sold in kVA but loads are counted in kW. Standby sets are normally quoted at a 0.8 power factor, so kW is 0.8 times kVA and a 500 kVA set delivers 400 kW. The chart below is computed, not copied, for every common size and system voltage, followed by the single phase table, kW to kVA at other power factors and the formulas.
Updated November 17, 2026
Generator kVA to kW and three phase amps, 208 to 600 volts
Full load amps at 0.8 power factor, three phase. Amps equal kVA times 1,000 divided by 1.732 times the line to line voltage. The kW column is kVA times 0.8. Find the set you have, read across to the voltage you run it at.
| Generator kVA | kW at 0.8 PF | Amps at 208 V | Amps at 240 V | Amps at 480 V | Amps at 600 V |
|---|---|---|---|---|---|
| 10 | 8.0 | 27.8 | 24.1 | 12.0 | 9.62 |
| 15 | 12.0 | 41.6 | 36.1 | 18.0 | 14.4 |
| 20 | 16.0 | 55.5 | 48.1 | 24.1 | 19.2 |
| 25 | 20.0 | 69.4 | 60.1 | 30.1 | 24.1 |
| 30 | 24.0 | 83.3 | 72.2 | 36.1 | 28.9 |
| 40 | 32.0 | 111 | 96.2 | 48.1 | 38.5 |
| 50 | 40.0 | 139 | 120 | 60.1 | 48.1 |
| 60 | 48.0 | 167 | 144 | 72.2 | 57.7 |
| 75 | 60.0 | 208 | 180 | 90.2 | 72.2 |
| 100 | 80.0 | 278 | 241 | 120 | 96.2 |
| 125 | 100.0 | 347 | 301 | 150 | 120 |
| 150 | 120.0 | 416 | 361 | 180 | 144 |
| 175 | 140.0 | 486 | 421 | 210 | 168 |
| 200 | 160.0 | 555 | 481 | 241 | 192 |
| 250 | 200.0 | 694 | 601 | 301 | 241 |
| 300 | 240.0 | 833 | 722 | 361 | 289 |
| 350 | 280.0 | 972 | 842 | 421 | 337 |
| 400 | 320.0 | 1,110 | 962 | 481 | 385 |
| 500 | 400.0 | 1,388 | 1,203 | 601 | 481 |
| 625 | 500.0 | 1,735 | 1,504 | 752 | 601 |
| 750 | 600.0 | 2,082 | 1,804 | 902 | 722 |
| 800 | 640.0 | 2,221 | 1,925 | 962 | 770 |
| 1,000 | 800.0 | 2,776 | 2,406 | 1,203 | 962 |
| 1,250 | 1,000.0 | 3,470 | 3,007 | 1,504 | 1,203 |
| 1,500 | 1,200.0 | 4,164 | 3,608 | 1,804 | 1,443 |
| 1,875 | 1,500.0 | 5,204 | 4,511 | 2,255 | 1,804 |
| 2,000 | 1,600.0 | 5,551 | 4,811 | 2,406 | 1,925 |
| 2,500 | 2,000.0 | 6,939 | 6,014 | 3,007 | 2,406 |
| 3,000 | 2,400.0 | 8,327 | 7,217 | 3,608 | 2,887 |
Free to cite with a link to this page. Every value is computed from kVA, voltage and 0.8 power factor. A 480 volt set is wired for 480 volts only if its nameplate says so. Many sets are reconnectable, so check the nameplate.
Medium voltage generator amps, 2,400 and 4,160 volts
Larger sets that feed a medium voltage bus run at 2,400 or 4,160 volts. The current is much lower than at 480 volts, which is why the feeder cable and breakers are smaller.
| Generator kVA | kW at 0.8 PF | Amps at 2,400 V | Amps at 4,160 V |
|---|---|---|---|
| 500 | 400.0 | 120 | 69.4 |
| 750 | 600.0 | 180 | 104 |
| 1,000 | 800.0 | 241 | 139 |
| 1,250 | 1,000.0 | 301 | 173 |
| 1,500 | 1,200.0 | 361 | 208 |
| 2,000 | 1,600.0 | 481 | 278 |
| 2,500 | 2,000.0 | 601 | 347 |
| 3,000 | 2,400.0 | 722 | 416 |
Single phase 120/240 volt generator chart
Single phase amps equal kVA times 1,000 divided by the voltage, with no 1.732. The 240 volt column is the line to line current, the 120 volt column is the current if the whole set were loaded on one leg, which is never the case in practice but is the figure for a single 120 volt circuit.
| Generator kVA | kW at 0.8 PF | Amps at 240 V | Amps at 120 V |
|---|---|---|---|
| 5 | 4.0 | 20.8 | 41.7 |
| 10 | 8.0 | 41.7 | 83.3 |
| 15 | 12.0 | 62.5 | 125 |
| 20 | 16.0 | 83.3 | 167 |
| 25 | 20.0 | 104 | 208 |
| 30 | 24.0 | 125 | 250 |
| 40 | 32.0 | 167 | 333 |
| 50 | 40.0 | 208 | 417 |
| 75 | 60.0 | 312 | 625 |
| 100 | 80.0 | 417 | 833 |
| 150 | 120.0 | 625 | 1,250 |
Home standby sets are often rated in kW at a different power factor, so use the nameplate kVA when it is given.
kW to kVA at four power factors
If you know the load in kW and want the generator in kVA, divide by the power factor. At 0.8 a 400 kW load needs 500 kVA. At 1.0 it needs 400 kVA. The generator must be sized for the kVA the load draws and also stay under its engine kW limit.
| Load kW | kVA at 0.80 PF | kVA at 0.85 PF | kVA at 0.90 PF | kVA at 1.00 PF |
|---|---|---|---|---|
| 20 | 25 | 23.5 | 22.2 | 20 |
| 30 | 37.5 | 35.3 | 33.3 | 30 |
| 40 | 50 | 47.1 | 44.4 | 40 |
| 50 | 62.5 | 58.8 | 55.6 | 50 |
| 60 | 75 | 70.6 | 66.7 | 60 |
| 75 | 93.8 | 88.2 | 83.3 | 75 |
| 100 | 125 | 117.6 | 111.1 | 100 |
| 125 | 156.2 | 147.1 | 138.9 | 125 |
| 150 | 187.5 | 176.5 | 166.7 | 150 |
| 200 | 250 | 235.3 | 222.2 | 200 |
| 250 | 312.5 | 294.1 | 277.8 | 250 |
| 300 | 375 | 352.9 | 333.3 | 300 |
| 400 | 500 | 470.6 | 444.4 | 400 |
| 500 | 625 | 588.2 | 555.6 | 500 |
| 600 | 750 | 705.9 | 666.7 | 600 |
| 750 | 937.5 | 882.4 | 833.3 | 750 |
| 800 | 1,000 | 941.2 | 888.9 | 800 |
| 1,000 | 1,250 | 1,176.5 | 1,111.1 | 1,000 |
| 1,500 | 1,875 | 1,764.7 | 1,666.7 | 1,500 |
| 2,000 | 2,500 | 2,352.9 | 2,222.2 | 2,000 |
Why standby generators are rated in kVA and loads in kW
A generator end is limited by the current in its windings, which is why it carries a kVA rating. The engine is limited by the power it can put on the shaft, which is why it carries a kW rating. The two are tied together by the rated power factor. Standby sets are conventionally rated at 0.8 lagging, so a set sold as 500 kVA is a 400 kW set.
A load with a power factor of 1.0, such as a resistive heater, uses the full engine kW but little more than 80 percent of the winding current. A load with a power factor under 0.8 hits the winding limit before the engine is fully loaded. Neither is a problem if the load is sized against both numbers.
Formulas and a worked example
Three phase amps equal kVA times 1,000 divided by 1.732 times volts. Single phase amps equal kVA times 1,000 divided by volts. kW equals kVA times power factor.
- A 750 kVA set at 480 volts three phase has 750 x 1,000 / (1.732 x 480) = 902 amps at full load and delivers 600 kW at 0.8 power factor.
- The same set at 4,160 volts has 104 amps.
- A 100 kW load at 0.9 power factor needs 111.1 kVA, which is 133.6 amps at 480 volts three phase. The next standard set is 125 or 150 kVA.
Matching generator amps to the breaker, transfer switch and transformer
The generator output breaker is sized to the full load amps in this chart, then rounded up to a standard breaker size. The transfer switch must be rated for at least that current, and for the available fault current. See the breaker size chart for the standard sizes.
A step up or step down transformer between the generator and the load is sized in kVA, the same unit as the set. Amps on each side come from the kVA and the voltage of that side. A 480 volt generator that feeds a 4,160 volt bus through a transformer sees the 480 volt current from this chart at the generator and the 4,160 volt current at the bus.
Common mistakes
Using the line to neutral voltage in the three phase formula, using 1.0 instead of 0.8 power factor for a set rated at 0.8, and mixing the kW and kVA columns of two different charts are the usual errors. Some published generator charts mix bases, so always check which power factor a chart uses.
- Use line to line voltage in the three phase formula, 480 for a 480Y/277 system.
- Check whether a rating in a catalog is kW or kVA before you read a row.
- A prime rated set and a standby rated set of the same frame carry different kW, so match the rating to the duty.
Common questions
How do you convert generator kVA to kW
Multiply kVA by the power factor. Standby generators are conventionally rated at 0.8 power factor, so kW equals kVA times 0.8. A 500 kVA generator is 400 kW and a 100 kVA generator is 80 kW.
How many amps is a 500 kVA generator
At 480 volts three phase a 500 kVA generator carries 601 amps at full load. At 208 volts it is 1,388 amps, at 600 volts 481 amps and at 4,160 volts 69 amps.
How many amps is a 100 kW generator
A 100 kW set at 0.8 power factor is 125 kVA. At 480 volts three phase that is 150 amps, at 208 volts 347 amps and at 240 volts 301 amps.
What is the generator kW to kVA formula
kVA equals kW divided by power factor. A 400 kW load at 0.8 power factor is 500 kVA, at 0.9 it is 444 kVA and at 1.0 it is 400 kVA.
Why is a generator rated in kVA and not just kW
The generator windings are limited by current, which is kVA, and the engine by shaft power, which is kW. The rated power factor ties the two together, and 0.8 is the usual standby figure.
Does single phase use the same formula
No. Single phase amps equal kVA times 1,000 divided by the voltage, with no 1.732. A 50 kVA single phase set at 240 volts carries 208 amps.
Related pages
Sources
Free to cite with a link to this page. Always check the edition of the code your inspector enforces.