Generators are sold in kVA but loads are counted in kW. Standby sets are normally quoted at a 0.8 power factor, so kW is 0.8 times kVA and a 500 kVA set delivers 400 kW. The chart below is computed, not copied, for every common size and system voltage, followed by the single phase table, kW to kVA at other power factors and the formulas.

Updated November 17, 2026

Generator kVA to kW and three phase amps, 208 to 600 volts

Full load amps at 0.8 power factor, three phase. Amps equal kVA times 1,000 divided by 1.732 times the line to line voltage. The kW column is kVA times 0.8. Find the set you have, read across to the voltage you run it at.

Generator kVAkW at 0.8 PFAmps at 208 VAmps at 240 VAmps at 480 VAmps at 600 V
108.027.824.112.09.62
1512.041.636.118.014.4
2016.055.548.124.119.2
2520.069.460.130.124.1
3024.083.372.236.128.9
4032.011196.248.138.5
5040.013912060.148.1
6048.016714472.257.7
7560.020818090.272.2
10080.027824112096.2
125100.0347301150120
150120.0416361180144
175140.0486421210168
200160.0555481241192
250200.0694601301241
300240.0833722361289
350280.0972842421337
400320.01,110962481385
500400.01,3881,203601481
625500.01,7351,504752601
750600.02,0821,804902722
800640.02,2211,925962770
1,000800.02,7762,4061,203962
1,2501,000.03,4703,0071,5041,203
1,5001,200.04,1643,6081,8041,443
1,8751,500.05,2044,5112,2551,804
2,0001,600.05,5514,8112,4061,925
2,5002,000.06,9396,0143,0072,406
3,0002,400.08,3277,2173,6082,887

Free to cite with a link to this page. Every value is computed from kVA, voltage and 0.8 power factor. A 480 volt set is wired for 480 volts only if its nameplate says so. Many sets are reconnectable, so check the nameplate.

Medium voltage generator amps, 2,400 and 4,160 volts

Larger sets that feed a medium voltage bus run at 2,400 or 4,160 volts. The current is much lower than at 480 volts, which is why the feeder cable and breakers are smaller.

Generator kVAkW at 0.8 PFAmps at 2,400 VAmps at 4,160 V
500400.012069.4
750600.0180104
1,000800.0241139
1,2501,000.0301173
1,5001,200.0361208
2,0001,600.0481278
2,5002,000.0601347
3,0002,400.0722416

Single phase 120/240 volt generator chart

Single phase amps equal kVA times 1,000 divided by the voltage, with no 1.732. The 240 volt column is the line to line current, the 120 volt column is the current if the whole set were loaded on one leg, which is never the case in practice but is the figure for a single 120 volt circuit.

Generator kVAkW at 0.8 PFAmps at 240 VAmps at 120 V
54.020.841.7
108.041.783.3
1512.062.5125
2016.083.3167
2520.0104208
3024.0125250
4032.0167333
5040.0208417
7560.0312625
10080.0417833
150120.06251,250

Home standby sets are often rated in kW at a different power factor, so use the nameplate kVA when it is given.

kW to kVA at four power factors

If you know the load in kW and want the generator in kVA, divide by the power factor. At 0.8 a 400 kW load needs 500 kVA. At 1.0 it needs 400 kVA. The generator must be sized for the kVA the load draws and also stay under its engine kW limit.

Load kWkVA at 0.80 PFkVA at 0.85 PFkVA at 0.90 PFkVA at 1.00 PF
202523.522.220
3037.535.333.330
405047.144.440
5062.558.855.650
607570.666.760
7593.888.283.375
100125117.6111.1100
125156.2147.1138.9125
150187.5176.5166.7150
200250235.3222.2200
250312.5294.1277.8250
300375352.9333.3300
400500470.6444.4400
500625588.2555.6500
600750705.9666.7600
750937.5882.4833.3750
8001,000941.2888.9800
1,0001,2501,176.51,111.11,000
1,5001,8751,764.71,666.71,500
2,0002,5002,352.92,222.22,000

Why standby generators are rated in kVA and loads in kW

A generator end is limited by the current in its windings, which is why it carries a kVA rating. The engine is limited by the power it can put on the shaft, which is why it carries a kW rating. The two are tied together by the rated power factor. Standby sets are conventionally rated at 0.8 lagging, so a set sold as 500 kVA is a 400 kW set.

A load with a power factor of 1.0, such as a resistive heater, uses the full engine kW but little more than 80 percent of the winding current. A load with a power factor under 0.8 hits the winding limit before the engine is fully loaded. Neither is a problem if the load is sized against both numbers.

Formulas and a worked example

Three phase amps equal kVA times 1,000 divided by 1.732 times volts. Single phase amps equal kVA times 1,000 divided by volts. kW equals kVA times power factor.

  • A 750 kVA set at 480 volts three phase has 750 x 1,000 / (1.732 x 480) = 902 amps at full load and delivers 600 kW at 0.8 power factor.
  • The same set at 4,160 volts has 104 amps.
  • A 100 kW load at 0.9 power factor needs 111.1 kVA, which is 133.6 amps at 480 volts three phase. The next standard set is 125 or 150 kVA.

Matching generator amps to the breaker, transfer switch and transformer

The generator output breaker is sized to the full load amps in this chart, then rounded up to a standard breaker size. The transfer switch must be rated for at least that current, and for the available fault current. See the breaker size chart for the standard sizes.

A step up or step down transformer between the generator and the load is sized in kVA, the same unit as the set. Amps on each side come from the kVA and the voltage of that side. A 480 volt generator that feeds a 4,160 volt bus through a transformer sees the 480 volt current from this chart at the generator and the 4,160 volt current at the bus.

Common mistakes

Using the line to neutral voltage in the three phase formula, using 1.0 instead of 0.8 power factor for a set rated at 0.8, and mixing the kW and kVA columns of two different charts are the usual errors. Some published generator charts mix bases, so always check which power factor a chart uses.

  • Use line to line voltage in the three phase formula, 480 for a 480Y/277 system.
  • Check whether a rating in a catalog is kW or kVA before you read a row.
  • A prime rated set and a standby rated set of the same frame carry different kW, so match the rating to the duty.

Common questions

How do you convert generator kVA to kW

Multiply kVA by the power factor. Standby generators are conventionally rated at 0.8 power factor, so kW equals kVA times 0.8. A 500 kVA generator is 400 kW and a 100 kVA generator is 80 kW.

How many amps is a 500 kVA generator

At 480 volts three phase a 500 kVA generator carries 601 amps at full load. At 208 volts it is 1,388 amps, at 600 volts 481 amps and at 4,160 volts 69 amps.

How many amps is a 100 kW generator

A 100 kW set at 0.8 power factor is 125 kVA. At 480 volts three phase that is 150 amps, at 208 volts 347 amps and at 240 volts 301 amps.

What is the generator kW to kVA formula

kVA equals kW divided by power factor. A 400 kW load at 0.8 power factor is 500 kVA, at 0.9 it is 444 kVA and at 1.0 it is 400 kVA.

Why is a generator rated in kVA and not just kW

The generator windings are limited by current, which is kVA, and the engine by shaft power, which is kW. The rated power factor ties the two together, and 0.8 is the usual standby figure.

Does single phase use the same formula

No. Single phase amps equal kVA times 1,000 divided by the voltage, with no 1.732. A 50 kVA single phase set at 240 volts carries 208 amps.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.

More charts

Wire ampacity chart from NEC Table 310.16
NEC Table 310.16 ampacities for copper and aluminum at 60, 75 and 90°C from 14 AWG to 2000 kcmil, with the terminal rule, small conductor limits and derating factors.
NEMA enclosure ratings chart
What NEMA Types 1, 3R, 4, 4X, 12 and the rest protect against, side by side, with the IP codes three published charts give for each and why they disagree.
Motor full load amps chart
Three phase motor full load amps from 1/2 to 500 HP at 115, 200, 208, 230, 460, 575 and 2300 V from NEC Table 430.250, single phase from 430.248, with wire, breaker and kVA by HP.
What size wire for every amp rating, 15 to 4000 amps
Wire size by amps from 15 to 400 A in copper and aluminum, the dwelling service sizes under NEC 310.12, and parallel sets for 400 to 4000 A services, with a calculator.
Primary distribution voltages, 4.16 kV to 34.5 kV
Every standard US primary voltage from 2.4 kV to 69 kV with its phase to ground value, wye or delta, insulation class and BIL, and what 12470Y/7200 on a nameplate means.
Commercial electrical service sizes, amps, kVA and transformer
Standard commercial service sizes from 100 to 4000 amps at 208Y/120 and 480Y/277 volts, the kVA each one carries, the transformer that feeds it, and when ground fault protection applies.
Breaker size chart, every standard breaker rating and its wire size
Every standard breaker size in NEC 240.6(A) from 10 to 6000 amps, the matching copper and aluminum wire size at 60 and 75°C, the 125 percent continuous load rule and common appliance circuits.
Transformer fuse size chart, primary full load amps by kVA and voltage
Primary full load amps for 25 to 2500 kVA three phase transformers at 4.16 to 34.5 kV, the NEC 450.3(B) 125 and 250 percent limits worked out at 480 V, and how pad mount fuses are chosen.
Copper bus bar ampacity chart, by bar size and temperature rise
Ampacity of 68 standard rectangular copper bus bar sizes from 1/16 by 1/2 inch to 3/4 by 12 inch at 30, 50 and 65 C rise, with area, weight and how to pick a bar for a transformer secondary.
Electrical service size chart, how many kW is a 200 amp service
kVA and kW for 60 to 1200 amp electrical services on single phase 240 volt and three phase 208, 240 and 480 volt systems, with 80 percent loading columns and the formula behind every figure.
Grounding electrode conductor size chart from NEC Table 250.66
NEC Table 250.66 grounding electrode conductor sizes in copper and aluminum, the 6 AWG rod rule and 4 AWG concrete encased rule, and the ground wire size for 100, 200, 400, 600, 800 and 1200 amp services.
How many acres does 1 MW of solar need
A utility scale solar farm needs about 5 to 10 acres per MWac. Fixed tilt averages 7.6 acres and single axis tracking 8.7 acres, with a table from 1 to 500 MW, panel counts and step up transformers.
Service wire size chart
Service entrance wire size for 100, 125, 150, 200, 225, 320, 400 and larger services in copper and aluminum, with the NEC 310.12 dwelling rule, parallel sets to 2000 amps, ground wire and the transformer behind the service.
NEMA plug and receptacle chart
NEMA plug chart for every straight blade and locking configuration, with voltage, poles, wires, amp ratings, the 80 percent continuous limit, how to read a name like 14-50R and L6-30P and which series fits 120, 208, 240 and 480 volts.
AWG wire gauge chart with diameter, mm2, kcmil and resistance
American wire gauge chart from 4/0 to 40 AWG with diameter in inches and mm, area in mm2 and kcmil, and copper resistance, plus a kcmil to mm2 table from 250 to 2000 kcmil.
CallGet a quote