Padmount Supply

Home / Guides / Meter Socket Generator Transfer Switches and How They Work

Meter Socket Generator Transfer Switches and How They Work

A meter socket transfer switch, also called a meter collar device, sits between the utility meter and the meter base. It lets a portable generator feed the whole house through the meter socket and keeps the house isolated from the utility line while the generator runs. The best known product is the GenerLink. This is a neutral explainer on how these devices work and what limits them, not a product page.

Updated November 20, 2026

What a meter collar transfer device is

A meter collar transfer device is a socket mounted switch. The utility meter plugs into the device and the device plugs into the meter base, so it sits directly behind the meter. A generator cord connects to it and the device feeds the panel through the service. A listing for the GenerLink describes it as UL listed, socket mounted and designed to connect a portable generator to a home.

How it keeps the house off the utility line

In normal operation the device passes utility power through to the house. When the generator is connected and the device is switched over, it opens the connection to the utility line and closes the connection to the generator, so the house cannot feed power back onto the line. That prevents backfeed, which endangers line crews working on a line that is supposed to be dead. A generator cord that plugs into a household outlet and backfeeds the panel does none of this, and is unsafe.

Service and generator size limits

A spec sheet for the GenerLink lists compatibility with a service of 200 amps or less, and one retailer listing adds that it fits a Form 2S meter base up to 200 amps. The generator side is smaller. The MA23-N is described as a 30 amp meter collar automatic transfer switch and a 40 amp version, the MA24, also exists. Those limits fall well under the 200 amp service, so the device suits a portable generator, not a large standby set. A building with a larger service or a standby generator uses a transfer switch rated for the service, see the comparison with an interlock kit.

Which utilities allow them

Rules vary, and utilities publish their own lists. AEP Texas lists specific GenerLink models as submitted to it and accepted for use as meter collar devices. PPL Electric does not allow customer owned meter collar devices to be installed between the utility billing meter and the meter base in the standard arrangement, though it permits a standalone installation downstream and says customers may use any device they choose subject to the local authority having jurisdiction. A GenerLink brochure says a standalone installation in a meter panel after the utility meter needs no utility approval and can be done by a licensed electrician. Those statements conflict, so ask the utility and the inspector before buying.

Comparison with an interlock kit and an automatic transfer switch

The three ways to connect a generator to a house differ in where they sit and what they cost to install.

Meter collar devicePanel interlock kitAutomatic transfer switch
Where it sitsBehind the meter, in the meter socketOn the main panel coverBeside the panel, wired to the service
Generator typePortable, the 30 and 40 amp models abovePortable, 30 or 50 amp inletStandby set with auto start
Utility involvementOften required or restricted, varies by utilityNormally the inspector onlyInspector and utility interconnect rules
Installed costNo dependable public price found$400 to $850 per HomeGuide$600 to $2,500 per HomeGuide
Automatic startSome models, check the maker dataNoYes

Installation and who may install it

A device in the meter socket is part of the service entrance, so work on it means the meter must be pulled or the service disconnected. Utilities control who may remove a meter, and some require a licensed electrician or their own crew. Do not pull a utility meter yourself. A meter collar device is also treated as utility metering equipment by some utilities, which is the reason for approval lists. Get written approval from the utility where it is required and a permit if the inspector wants one.

What it has to do with the service transformer

The utility transformer outside, a pad mount or a pole top unit, is not touched by any of this. The device isolates the house from the utility secondary and lets a small generator supply the house side only. That isolation is what keeps the generator from energizing the transformer secondary and, through it, the primary line, which is the backfeed hazard linemen worry about.

Related pages

Common questions

What is a GenerLink

A GenerLink is a socket mounted transfer device that goes between the utility meter and the meter base so a portable generator can power a home while the house is isolated from the utility line.

How many amps does a meter collar transfer switch handle

The GenerLink spec sheet lists compatibility with a service of 200 amps or less. The generator side is lower. The MA23-N is a 30 amp model and the MA24 a 40 amp model.

Do I need utility approval for a meter collar transfer switch

It depends on the utility. AEP Texas keeps a list of accepted models. PPL Electric does not allow customer owned devices between its meter and meter base in the standard arrangement. A maker brochure says a standalone installation after the meter needs no utility approval. Ask your utility.

Is a meter collar transfer switch better than an interlock kit

Neither is better in every case. A meter collar device mounts at the meter and needs nothing changed in the panel, and an interlock kit mounts in the panel and costs $400 to $850 installed per HomeGuide. Utility rules often decide.

Can I install a meter collar transfer switch myself

It sits in the service entrance and the meter has to be removed, which utilities control. A licensed electrician and the utility should be involved.

Sources

Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.

More guides

CallGet a quote