Home / Guides / Automatic Transfer Switch, How It Works and Sizes

Automatic Transfer Switch, How It Works and Sizes

An automatic transfer switch, or ATS, moves a building's load from the utility to a generator when the utility fails, and back when it returns. It never connects the two sources to the load at the same time unless it is a closed transition type built to do so. Size it to the load amps and the available fault current, not to the generator alone.

Updated November 20, 2026

What an automatic transfer switch does

An ATS watches the normal source, usually the utility. When that source fails, the controls start the generator, wait for it to reach voltage and frequency, then move the load to it. When the utility is back and stable, the switch retransfers the load and the generator shuts down. A mechanical interlock keeps the two sources from being connected together through the switch in the standard design (Cummins application manual). That interlock is also why a transfer switch prevents backfeed onto utility lines, which is the danger that makes a bare generator connection unsafe for line workers.

Open, closed and delayed transition

Open transition is break before make. The load is disconnected from one source before it is connected to the other. Cummins puts the gap at roughly 3 to 5 cycles, 50 to 80 milliseconds, for an in phase transfer, and notes it suits resistive and small motor loads. The TSEWG guide says open transition is usually the choice for utility to generator transfers because it avoids momentarily paralleling the generator with the utility. Closed transition is make before break, so there is no interruption, and the equipment acts as open transition when one source has failed. TSEWG warns that a switch failure during a closed transition could leave both sources connected to the load. Open delayed transition is a three position design that pauses in a neutral position for a programmable time, which lets large motors and transformer inrush decay, and can shed load (Generac).

Bypass isolation and static transfer switches

A bypass isolation switch adds a second path, so the ATS can be withdrawn and serviced while the load stays powered from either source. Eaton lists contactor type bypass isolation switches from 100 to 3,000 amps up to 600 volts, Cummins lists its bypass isolation line from 150 to 4,000 amps, and Generac lists a 100 to 1,200 amp bypass isolation line. A static transfer switch uses solid state devices instead of moving contacts, which is a different product for data center and critical loads where even a few cycles matter. The sources we read cover bypass isolation in detail and static switches only in passing, so confirm static switch ratings with the maker.

NEC classes and where they apply

Transfer equipment is classed by the kind of system it serves. Article 700 covers emergency systems, 701 legally required standby systems, 702 optional standby systems and 708 critical operations power systems, with health care facilities under 517 (IEEE ATS 101 and the Eaton design guide). Generac notes that 702 systems are not mandated by a government agency, unlike 700 and 701. We did not read the NEC text itself, so check what each article requires of the switch, including whether closed transition is permitted, against the NFPA 70 edition your inspector enforces.

Sizing an ATS

Size the switch for the load it carries, in amps, at the system voltage, and check its withstand rating against the available fault current. The table shows full load amps a generator of a given kW produces, assuming a 0.8 power factor, as a starting point only. It is arithmetic, kW divided by 0.8, times 1,000, divided by 1.732 times the line voltage, rounded to a whole amp. The load actually on the switch can be smaller, and the service rating, the generator breaker and local rules all matter.

GeneratorAmps at 208 V three phaseAmps at 480 V three phase
30 kW10445
60 kW20890
100 kW347150
150 kW520226
250 kW867376
500 kW1,735752
1000 kW3,4701,504
2000 kW6,9393,007

Ratings you will see on products

The sources we read do not give one ladder of ratings that every maker follows. Published ranges differ by product, for example Cummins standard transfer switches from 40 to 600 amps and Caterpillar bypass isolation power breaker units from 200 to 5,000 amps. Caterpillar lists those units as UL 1008 up to 3,200 amps and UL 891 at 4,000 and 5,000 amps, so a UL 1008 requirement at 4,000 amps needs checking against the exact model. Pick the frame from the maker's current catalog and match the pole count, voltage and short circuit rating to your single line drawing.

Where the ATS sits in the system

On a building with a pad mounted transformer, the utility transformer feeds the service, and the ATS sits downstream of the service equipment for non service rated types, or at the service for service entrance rated types. For the equipment ahead of the switch, see our pad mounted transformer pages, and for the switchgear around it, see what is switchgear.

Buying and replacing one

For a replacement, copy the nameplate amps, voltage, poles, short circuit rating, control model and transition type. Ask the seller about lead time in writing. For ASCO models by series and amps, see our ASCO transfer switch page, and to price a switch with a generator, use the quote form.

Related pages

Common questions

What is an automatic transfer switch

It is a switch that moves a building's load from the utility to a generator when the utility fails, then back when power returns, with no one touching it.

How does an automatic transfer switch work

It senses the normal source, signals the generator to start, waits for acceptable voltage and frequency, transfers the load, and retransfers after the utility is stable.

What is the difference between open and closed transition

Open transition breaks one source before making the other, so there is a brief gap. Closed transition makes the new source first, so there is no gap.

Is an ATS the same as a manual transfer switch

No. A manual switch needs a person to move the handle. The automatic type does it from sensing and a control.

What size automatic transfer switch do I need

Match the load amps and voltage, then check the switch's short circuit rating against the available fault current. The generator amp table on this page gives a starting point.

Sources

Free to cite with a link to this page. Work out current at any rating with the kVA to amps calculator.