Home / Products / Switchgear / 4000 amp switchboard
4000 amp switchboard
A 4000 amp switchboard serves a 2500 to 3000 kVA transformer at 480 V, about 3,007 to 3,608 A at full load, or a large data center or industrial feeder. At this size the main is a power breaker or a pair of sources, not a molded case unit. We source new and reconditioned lineups and quote them delivered.
Updated November 17, 2026
Match the switchboard to the transformer
A 4000 A bus carries up to about 3,326 kVA at 480 V. Many large sites split the load across two transformers and a tie breaker instead.
| Transformer | Full load current |
|---|---|
| 2,500 kVA at 480 V | 3,007 A |
| 3,000 kVA at 480 V | 3,608 A |
| 3,500 kVA at 480 V | 4,210 A |
| 1000 kVA at 208 V | 2,776 A |
| 1500 kVA at 208 V | 4,164 A |
Computed from the three phase formula. Check the largest transformer rating your utility and code allow.
Main device at 4000 A
Eaton lists Magnum SB insulated case frames only to 3000 A, and its Magnum DS power breakers cover 1200 A up to 5000 A. Siemens lists WL breakers up to 4000 A and ABB lists Power Break II to 4000 A. Schneider's Power-Style QED-2 brochure shows through bus from about 1,200 to 5,000 A and individually mounted feeders up to 4000 A.
In practice a 4000 A main means a drawout power or insulated case breaker on a rated bus, with sections sized for the bus. Sections are wider and deeper than a 2000 A lineup, so confirm the room before you order.
Quick ship programs and lead time
Vertiv runs a quick ship program for pre configured 4000 A switchboards and says it cuts lead time against conventional engineered builds. A dealer listing for new Siemens switchboards states quick ship 6 to 8 weeks and custom 10 to 12 weeks. Both are seller claims, not independent figures, and a 4000 A custom lineup can run longer. See the lead time page.
Used and reconditioned
Reconditioned 4000 A Square D, GE, Siemens and Westinghouse lineups appear on the used market. Match breaker frames, bus bracing and the short circuit rating to your fault study before buying.
What to send for a quote
- System voltage, for example 480Y/277 V three phase four wire
- Main bus amps and the short circuit rating in kA
- Main device, breaker or fusible switch, and the feeder schedule
- Indoor NEMA 1 or outdoor NEMA 3R, and service entrance or not
- New, new surplus or reconditioned, and the date you need it on site
- A photo of the nameplate if you are matching an existing lineup
- Delivery ZIP code
Common questions
What size transformer needs a 4000 amp switchboard
At 480 V, 4000 A is about 3,326 kVA. A 2500 kVA unit draws about 3,007 A and a 3000 kVA unit about 3,608 A.
What main breaker goes in a 4000 amp switchboard
A power or large insulated case breaker. Siemens WL and ABB Power Break II go to 4000 A, and Eaton Magnum DS reaches 5000 A.
How long does a 4000 amp switchboard take
Quick ship programs claim weeks and custom builds run much longer. We quote current lead times for the specific unit.
Can I buy a used 4000 amp switchboard
Yes. Send the nameplate and the one line diagram and we will source matching reconditioned units.
Related pages
Sources
- Eaton, Magnum SB, Magnum DS and Magnum IEC technical product manual
- Siemens, switchboards and low voltage power distribution guide
- ABB, Power Break II insulated case circuit breakers
- Schneider Electric, Power-Style QED-2 switchboard brochure
- Vertiv, Powerboard UL 891 switchboard quick ship program
- Surplus Record, new Siemens switchboards quick ship listing
- Surplus Record, used Square D QED switchboard listings
Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.