Padmount Supply

Home / Products / Switchgear / 2000 amp switchboard

2000 amp switchboard

A 2000 amp switchboard is the usual main for a 1500 kVA transformer at 480 V, about 1,804 A at full load. It is a UL 891 lineup with an insulated case or power breaker main, or a bolted pressure switch. We source new, surplus and reconditioned units and quote them delivered.

Updated November 17, 2026

Match the switchboard to the transformer

A 2000 A bus carries up to about 1,663 kVA at 480 V. The 1500 kVA pad mounted transformer is the common pairing, and it leaves little margin, so some designs step up to 2500 A.

TransformerFull load current
1,500 kVA at 480 V1,804 A
2,000 kVA at 480 V2,406 A
500 kVA at 208 V1,388 A
750 kVA at 208 V2,082 A

Computed from the three phase formula. Code margins and utility rules decide the final service rating.

Makers and lines

Square D sells the QED-2 and Power-Style lines, and its brochure lists through bus from about 1,200 to 5,000 A with Masterpact NW mains. Eaton builds Pow-R-Line C and lists 2000 A insulated case frames in its Magnum SB breaker. Siemens sells SB1, SB2 and SB3 switchboards, and lists WL insulated case breakers up to 4000 A.

Size

Section size depends on maker, depth and feed. Used Square D 2000 A listings read in November 2026 show main sections about 36 in wide, 48 to 60 in deep and 90 to 91 in tall, with distribution sections wider. Eaton gives 90 in as its standard height with custom heights on request. Treat these as examples and get the submittal for the exact unit, because depth and top or bottom feed change the room you need.

Lead time and condition

New 480 V lineups from major makers run 16 to 26 weeks in a 2026 industry article, and some sources give longer. Reconditioned stock ships faster. Our lead time page lists the figures and sources.

What to send for a quote

  • System voltage, for example 480Y/277 V three phase four wire
  • Main bus amps and the short circuit rating in kA
  • Main device, breaker or fusible switch, and the feeder schedule
  • Indoor NEMA 1 or outdoor NEMA 3R, and service entrance or not
  • New, new surplus or reconditioned, and the date you need it on site
  • A photo of the nameplate if you are matching an existing lineup
  • Delivery ZIP code

Common questions

What size transformer goes with a 2000 amp switchboard

At 480 V, a 1500 kVA transformer draws about 1,804 A and a 2000 kVA unit about 2,406 A. A 2000 A bus covers up to about 1,663 kVA.

What are the dimensions of a 2000 amp switchboard

Dealer listings for used Square D units show main sections about 36 in wide and 90 to 91 in tall, with depth from 48 to 60 in. Eaton lists a standard height of 90 in. Get the maker submittal for an exact unit.

Is a 2000 amp switchboard the same as 2000 amp switchgear

Not strictly. Switchboards follow UL 891 and switchgear follows UL 1558 with drawout power breakers. Many listings use the words loosely.

Can you supply a used 2000 amp switchboard

Yes, we source reconditioned lineups from Square D, Eaton, Siemens and GE. Send the nameplate details and the delivery ZIP code.

Related pages