Breaker size for 150 kVA transformer

A 150 kVA three phase transformer on a 480 V primary draws 180 amps, so the primary breaker is 250 amps when only the primary is protected, and 450 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 416 amps and takes a breaker of 600 amps at most. Updated 25 November 2026.

Updated November 25, 2026

150 kVA transformer full load current, breaker and wire size

One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.

VoltageFull load ampsBreaker, 125 percentCopper, 75 CAluminum, 75 C
208 V three phase416 A600 A1500 kcmilParallel sets
240 V three phase361 A500 A900 kcmil1500 kcmil
480 V three phase180 A250 A250 kcmil350 kcmil
600 V three phase144 A200 A3/0 AWG250 kcmil

Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.

Breaker size for a 150 kVA transformer, primary and secondary

NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).

Primary voltagePrimary full loadPrimary only, up toWith secondary breaker, primary up to
208 V416 A600 A1000 A, not above 1,041 A
240 V361 A500 A800 A, not above 902 A
480 V180 A250 A450 A, not above 451 A
600 V144 A200 A350 A, not above 361 A

A 480 to 208Y/120 volt 150 kVA unit therefore takes a 250 amp primary breaker alone, or up to a 450 amp primary with a 600 amp breaker on the secondary. Any standard size between those two limits is allowed.

Wire size and ground size for a 150 kVA transformer

Wire size follows the breaker. On a 480 V primary that is 250 kcmil copper or 350 kcmil aluminum at 250 amps. On the 208 V secondary it is 1500 kcmil copper, or parallel sets in aluminum at 600 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With 1500 kcmil copper on the secondary that is 8 AWG copper, and with 250 kcmil on the primary it is 2 AWG copper. The full table is on the grounding electrode conductor size chart.

Fuse size for a 150 kVA transformer

On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 250 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.

Medium voltage primaryFull load amps, 150 kVA three phase
12,470 V6.9 A
13,200 V6.6 A

That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.

Single phase 150 kVA transformer, breaker and amps

Single phase voltageFull load ampsBreaker, 125 percent
240 V625 A800 A
480 V313 A400 A

Single phase current is kVA times 1000 divided by the voltage, no root three.

Worked example, 480 V to 208Y/120 V

A shop needs a 150 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 150 times 1000 divided by 480 times 1.732, which is 180 amps. Times 1.25 is 226 amps, so the next standard breaker is 250 amps with 250 kcmil copper. Secondary current is 416 amps, times 1.25 is 520 amps, so the secondary breaker is 600 amps and the conductors are 1500 kcmil copper, or parallel sets in aluminum. The 600 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.

Where the 150 kVA unit comes from

Indoors, a dry type unit, see the 150 kVA dry type transformer. Outdoors on a pad, the 150 kVA pad mounted transformer, with its dimensions, weight and prices. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.

Get a 150 kVA transformer quoted

Questions

What size breaker for a 150 kVA transformer?

On a three phase 480 V primary the full load current is 180 amps, so a primary breaker of 250 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 416 amps and the largest secondary breaker is 600 amps.

What size wire for a 150 kVA transformer?

For the 250 amp primary breaker, 250 kcmil copper or 350 kcmil aluminum from the 75 C column of NEC Table 310.16. For the 600 amp secondary breaker, 1500 kcmil copper, or parallel sets in aluminum.

What size fuse for a 150 kVA transformer?

A dry type unit on a 480 V primary uses the same limits as a breaker, up to 250 amps for primary only protection. A 150 kVA pad mount on 12470 volts draws only 6.9 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.

How many amps does a 150 kVA transformer draw?

180 amps at 480 V three phase, 416 amps at 208 V, 361 amps at 240 V and 144 amps at 600 V. Single phase it is 625 amps at 240 V.

What size breaker for a 150 kVA transformer 480 to 240 volts single phase?

A single phase 150 kVA transformer from 480 V to 240 V draws 313 amps on the 480 V primary, so a primary breaker of 400 amps is the usual size when only the primary is protected. The 240 V secondary carries 625 amps, with a largest secondary breaker of 800 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).

What is the primary and secondary current of a 150 kVA transformer?

For 480 to 208Y/120 volts, 180 amps on the primary and 416 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.