Transformer breaker, wire and fuse size by kVA

Pick a rating to see the breaker, wire, fuse and ground size for it, primary and secondary, with the amps worked out. More ratings are added each week.

Updated November 25, 2026

1 kVA and 10 kVA transformer, 480 to 120 and 480 to 208

Small control and lighting units are asked for by voltage pair. Single phase current is kVA times 1000 divided by the voltage. Three phase divides by the voltage times 1.732 as well.

TransformerPrimary amps at 480 VSecondary amps
1 kVA 480 to 120 transformer, single phase2.1 A8.3 A at 120 V
10 kVA 480 to 120 transformer, single phase20.8 A83.3 A at 120 V
10 kVA 480 to 208 transformer, three phase12.0 A27.8 A at 208 V
10 kVA 480 to 208 transformer, single phase20.8 A48.1 A at 208 V

For any other rating use the kVA to amps calculator, the breaker size chart and the transformer fuse size chart. Sizes of the transformers themselves are on transformer sizes.

Smaller three phase units are asked for as the breaker size for a 45 kVA transformer too.

Smallest rating, the breaker size for a 3 kVA transformer, the breaker size for a 5 kVA transformer, the breaker size for a 7.5 kVA transformer, the breaker size for a 9 kVA transformer, the breaker size for a 10 kVA transformer, the breaker size for a 37.5 kVA transformer, the breaker size for a 167 kVA transformer, the breaker size for a 300 kVA transformer, the breaker size for a 500 kVA transformer, the breaker size for a 750 kVA transformer, with 14 and 12 AWG wire. Next up, the breaker size for a 15 kVA transformer. Small three phase ratings too, the breaker size for a 30 kVA transformer.

Larger three phase ratings too, the breaker size for a 150 kVA transformer and breaker size for a 112.5 kVA transformer. Terminal connections are in how to wire a transformer.

Sizing the wire side too? The service wire size chart and the copper bus bar ampacity chart give conductor and bus limits, the NEMA plug chart covers small loads, and what switchgear is explains the gear downstream. For the 125 kVA unit see the 125 kVA transformer, and for resale see used power transformers.

Related reading, the 125 kVA transformer sizes and dimensions, what switchgear is for the gear fed from the secondary, the NEMA plug chart for small loads, and used power transformers when the lead time on a new unit is too long.

Between 75 and 150 kVA too, the breaker size for a 100 kVA transformer.

Above 150 kVA, the breaker size for a 225 kVA transformer has the amps, breaker, wire and fuse limits worked out.