Grounding electrode conductor size chart from NEC Table 250.66

The grounding electrode conductor, or GEC, is the wire from the service or transformer grounding point to the ground rods, water pipe, building steel or concrete encased electrode. NEC Table 250.66 sizes it from the largest ungrounded service conductor, not from the breaker rating. A 200 amp service with 3/0 copper conductors needs a 4 AWG copper GEC, and the table never asks for more than 3/0 copper. The full table comes first, then the electrode caps that let you go smaller, then the answer for each common service size.

Updated November 16, 2026

NEC Table 250.66, grounding electrode conductor for alternating current systems

Enter the table with the size of the largest ungrounded service entrance conductor, or the equivalent area when conductors run in parallel. Copper and aluminum service conductors have their own columns, and the GEC can be either material. Aluminum or copper clad aluminum GECs have installation limits, covered below.

Largest ungrounded service conductor, copperLargest ungrounded service conductor, aluminum or copper clad aluminumGEC, copperGEC, aluminum or copper clad aluminum
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 AWG or 1/0 AWG2/0 AWG or 3/0 AWG6 AWG4 AWG
2/0 AWG or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 AWG through 350 kcmilOver 250 kcmil through 500 kcmil2 AWG1/0 AWG
Over 350 kcmil through 600 kcmilOver 500 kcmil through 900 kcmil1/0 AWG3/0 AWG
Over 600 kcmil through 1100 kcmilOver 900 kcmil through 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil

The caps that let the GEC be smaller than the table

Table 250.66 gives the minimum for the full system. Sections 250.66(A), (B) and (C) then cap how large the conductor has to be on the last run, because some electrodes cannot use more copper than a small wire already delivers. The caps apply only where no other electrode that needs a bigger conductor, such as an underground metal water pipe, is connected to that electrode.

ElectrodeRuleLargest GEC required
Ground rod, pipe or plate250.66(A)6 AWG copper or 4 AWG aluminum
Concrete encased electrode (Ufer)250.66(B)4 AWG copper, aluminum is not permitted for this connection
Ground ring250.66(C)No larger than the ring conductor itself. The ring is at least 2 AWG copper under 250.52(A)(4)
Any electrodeTable 250.66Never more than 3/0 AWG copper or 250 kcmil aluminum

Ground wire size by service size, 100 to 1200 amps

These sizes assume the service conductors are sized at the full service rating from the 75°C column of NEC Table 310.16, using the values on our wire ampacity chart. Larger services use parallel sets, shown in the table. Your design may choose different conductors, and then the GEC row changes with them. The last run to a rod is still 6 AWG copper at most.

ServiceCopper service conductorsGEC for copper serviceAluminum service conductorsGEC for aluminum service
100 A3 AWG8 AWG copper or 6 AWG aluminum1 AWG8 AWG copper or 6 AWG aluminum
200 A3/0 AWG4 AWG copper or 2 AWG aluminum250 kcmil4 AWG copper or 2 AWG aluminum
400 A600 kcmil1/0 AWG copper or 3/0 AWG aluminum900 kcmil1/0 AWG copper or 3/0 AWG aluminum
600 A2 sets of 350 kcmil2/0 AWG copper or 4/0 AWG aluminum2 sets of 500 kcmil2/0 AWG copper or 4/0 AWG aluminum
800 A2 sets of 600 kcmil3/0 AWG copper or 250 kcmil aluminum2 sets of 900 kcmil3/0 AWG copper or 250 kcmil aluminum
1200 A4 sets of 350 kcmil3/0 AWG copper or 250 kcmil aluminum4 sets of 500 kcmil3/0 AWG copper or 250 kcmil aluminum

Computed from Table 310.16 at 75°C and Table 250.66. Check the code edition your state has adopted.

Worked examples

A 200 amp residential service has 2/0 copper ungrounded conductors and the GEC goes to a water pipe. The 2/0 or 3/0 row gives 4 AWG copper. A 400 amp commercial service with two parallel sets of 250 kcmil copper totals 500 kcmil, which falls in the over 350 through 600 row and gives 1/0 AWG copper. An 800 amp service with two sets of 600 kcmil totals 1200 kcmil, above 1100, so it needs 3/0 copper. Run a single wire from that service to a driven rod and 6 AWG copper is enough.

Transformers and separately derived systems

The same table sizes the GEC for a separately derived system such as a dry type transformer secondary. The input is the largest ungrounded conductor of the derived system. If a transformer secondary runs 4/0 copper, the GEC is 2 AWG copper. Find the secondary current for any kVA and voltage with our transformer sizing calculator.

GEC is not the equipment grounding conductor

The GEC ties the system to earth and is sized from the conductor size in Table 250.66. The equipment grounding conductor, or EGC, rides with the circuit conductors and is sized in Table 250.122 from the rating of the breaker or fuse protecting that circuit. Mixing the two tables up is the most common error on ground wire charts. A 200 amp breaker sets the EGC and the service conductor size sets the GEC.

Why substations and plants use bigger wire than the code asks for

Industrial facilities often install 4/0 copper to every electrode even though the table allows 6 AWG at a rod. One engineering reference notes that IEEE 80 usually prefers 2/0 stranded copper in the field for mechanical strength, even where a fault current calculation would allow 4 AWG. That is a design choice, not a code minimum, and anything larger than the table is allowed.

Common questions

What size ground wire for a 200 amp service

For 3/0 copper or 250 kcmil aluminum service conductors the GEC is 4 AWG copper or 2 AWG aluminum under Table 250.66. If the wire only runs to a driven rod, 6 AWG copper is enough.

What size ground wire for a 100 amp service

With 3 AWG copper service conductors the table gives 8 AWG copper, or 6 AWG aluminum. A rod connection can use 6 AWG copper regardless.

What size grounding electrode conductor for a 400 amp service

A single set of 600 kcmil copper conductors falls in the over 350 through 600 kcmil row, so the GEC is 1/0 copper or 3/0 aluminum. A rod connection is still capped at 6 AWG copper.

What is the largest grounding electrode conductor the NEC requires

Table 250.66 stops at 3/0 AWG copper or 250 kcmil aluminum, even for very large services.

What size wire goes to a ground rod

No larger than 6 AWG copper or 4 AWG aluminum under 250.66(A), unless another electrode needing a larger conductor is connected to the same run.

What size conductor goes to a Ufer ground

No larger than 4 AWG copper under 250.66(B). Aluminum is not permitted for that connection.

Is the grounding electrode conductor sized from the breaker

No. Table 250.66 uses the size of the largest ungrounded service conductor. The equipment grounding conductor is the one sized from the breaker rating.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.

More charts

Wire ampacity chart from NEC Table 310.16
NEC Table 310.16 ampacities for copper and aluminum at 60, 75 and 90°C from 14 AWG to 2000 kcmil, with the terminal rule, small conductor limits and derating factors.
NEMA enclosure ratings chart
What NEMA Types 1, 3R, 4, 4X, 12 and the rest protect against, side by side, with the IP codes three published charts give for each and why they disagree.
Motor full load amps chart
Three phase motor full load amps from 1/2 to 500 HP at 115, 200, 208, 230, 460, 575 and 2300 V from NEC Table 430.250, single phase from 430.248, with wire, breaker and kVA by HP.
What size wire for every amp rating, 15 to 4000 amps
Wire size by amps from 15 to 400 A in copper and aluminum, the dwelling service sizes under NEC 310.12, and parallel sets for 400 to 4000 A services, with a calculator.
Primary distribution voltages, 4.16 kV to 34.5 kV
Every standard US primary voltage from 2.4 kV to 69 kV with its phase to ground value, wye or delta, insulation class and BIL, and what 12470Y/7200 on a nameplate means.
Commercial electrical service sizes, amps, kVA and transformer
Standard commercial service sizes from 100 to 4000 amps at 208Y/120 and 480Y/277 volts, the kVA each one carries, the transformer that feeds it, and when ground fault protection applies.
Breaker size chart, every standard breaker rating and its wire size
Every standard breaker size in NEC 240.6(A) from 10 to 6000 amps, the matching copper and aluminum wire size at 60 and 75°C, the 125 percent continuous load rule and common appliance circuits.
Transformer fuse size chart, primary full load amps by kVA and voltage
Primary full load amps for 25 to 2500 kVA three phase transformers at 4.16 to 34.5 kV, the NEC 450.3(B) 125 and 250 percent limits worked out at 480 V, and how pad mount fuses are chosen.
Copper bus bar ampacity chart, by bar size and temperature rise
Ampacity of 68 standard rectangular copper bus bar sizes from 1/16 by 1/2 inch to 3/4 by 12 inch at 30, 50 and 65 C rise, with area, weight and how to pick a bar for a transformer secondary.
Electrical service size chart, how many kW is a 200 amp service
kVA and kW for 60 to 1200 amp electrical services on single phase 240 volt and three phase 208, 240 and 480 volt systems, with 80 percent loading columns and the formula behind every figure.
How many acres does 1 MW of solar need
A utility scale solar farm needs about 5 to 10 acres per MWac. Fixed tilt averages 7.6 acres and single axis tracking 8.7 acres, with a table from 1 to 500 MW, panel counts and step up transformers.
Generator kVA to kW and amps chart
Generator kVA to kW and full load amps for 10 to 3,000 kVA at 120/240, 208, 240, 480, 600, 2,400 and 4,160 volts, computed at 0.8 power factor, with kW to kVA at other power factors.
Service wire size chart
Service entrance wire size for 100, 125, 150, 200, 225, 320, 400 and larger services in copper and aluminum, with the NEC 310.12 dwelling rule, parallel sets to 2000 amps, ground wire and the transformer behind the service.
NEMA plug and receptacle chart
NEMA plug chart for every straight blade and locking configuration, with voltage, poles, wires, amp ratings, the 80 percent continuous limit, how to read a name like 14-50R and L6-30P and which series fits 120, 208, 240 and 480 volts.
AWG wire gauge chart with diameter, mm2, kcmil and resistance
American wire gauge chart from 4/0 to 40 AWG with diameter in inches and mm, area in mm2 and kcmil, and copper resistance, plus a kcmil to mm2 table from 250 to 2000 kcmil.
CallGet a quote