Home / Charts / Grounding electrode conductor size chart from NEC Table 250.66
Grounding electrode conductor size chart from NEC Table 250.66
The grounding electrode conductor, or GEC, is the wire from the service or transformer grounding point to the ground rods, water pipe, building steel or concrete encased electrode. NEC Table 250.66 sizes it from the largest ungrounded service conductor, not from the breaker rating. A 200 amp service with 3/0 copper conductors needs a 4 AWG copper GEC, and the table never asks for more than 3/0 copper. The full table comes first, then the electrode caps that let you go smaller, then the answer for each common service size.
Updated November 16, 2026
NEC Table 250.66, grounding electrode conductor for alternating current systems
Enter the table with the size of the largest ungrounded service entrance conductor, or the equivalent area when conductors run in parallel. Copper and aluminum service conductors have their own columns, and the GEC can be either material. Aluminum or copper clad aluminum GECs have installation limits, covered below.
| Largest ungrounded service conductor, copper | Largest ungrounded service conductor, aluminum or copper clad aluminum | GEC, copper | GEC, aluminum or copper clad aluminum |
|---|---|---|---|
| 2 AWG or smaller | 1/0 AWG or smaller | 8 AWG | 6 AWG |
| 1 AWG or 1/0 AWG | 2/0 AWG or 3/0 AWG | 6 AWG | 4 AWG |
| 2/0 AWG or 3/0 AWG | 4/0 AWG or 250 kcmil | 4 AWG | 2 AWG |
| Over 3/0 AWG through 350 kcmil | Over 250 kcmil through 500 kcmil | 2 AWG | 1/0 AWG |
| Over 350 kcmil through 600 kcmil | Over 500 kcmil through 900 kcmil | 1/0 AWG | 3/0 AWG |
| Over 600 kcmil through 1100 kcmil | Over 900 kcmil through 1750 kcmil | 2/0 AWG | 4/0 AWG |
| Over 1100 kcmil | Over 1750 kcmil | 3/0 AWG | 250 kcmil |
The caps that let the GEC be smaller than the table
Table 250.66 gives the minimum for the full system. Sections 250.66(A), (B) and (C) then cap how large the conductor has to be on the last run, because some electrodes cannot use more copper than a small wire already delivers. The caps apply only where no other electrode that needs a bigger conductor, such as an underground metal water pipe, is connected to that electrode.
| Electrode | Rule | Largest GEC required |
|---|---|---|
| Ground rod, pipe or plate | 250.66(A) | 6 AWG copper or 4 AWG aluminum |
| Concrete encased electrode (Ufer) | 250.66(B) | 4 AWG copper, aluminum is not permitted for this connection |
| Ground ring | 250.66(C) | No larger than the ring conductor itself. The ring is at least 2 AWG copper under 250.52(A)(4) |
| Any electrode | Table 250.66 | Never more than 3/0 AWG copper or 250 kcmil aluminum |
Ground wire size by service size, 100 to 1200 amps
These sizes assume the service conductors are sized at the full service rating from the 75°C column of NEC Table 310.16, using the values on our wire ampacity chart. Larger services use parallel sets, shown in the table. Your design may choose different conductors, and then the GEC row changes with them. The last run to a rod is still 6 AWG copper at most.
| Service | Copper service conductors | GEC for copper service | Aluminum service conductors | GEC for aluminum service |
|---|---|---|---|---|
| 100 A | 3 AWG | 8 AWG copper or 6 AWG aluminum | 1 AWG | 8 AWG copper or 6 AWG aluminum |
| 200 A | 3/0 AWG | 4 AWG copper or 2 AWG aluminum | 250 kcmil | 4 AWG copper or 2 AWG aluminum |
| 400 A | 600 kcmil | 1/0 AWG copper or 3/0 AWG aluminum | 900 kcmil | 1/0 AWG copper or 3/0 AWG aluminum |
| 600 A | 2 sets of 350 kcmil | 2/0 AWG copper or 4/0 AWG aluminum | 2 sets of 500 kcmil | 2/0 AWG copper or 4/0 AWG aluminum |
| 800 A | 2 sets of 600 kcmil | 3/0 AWG copper or 250 kcmil aluminum | 2 sets of 900 kcmil | 3/0 AWG copper or 250 kcmil aluminum |
| 1200 A | 4 sets of 350 kcmil | 3/0 AWG copper or 250 kcmil aluminum | 4 sets of 500 kcmil | 3/0 AWG copper or 250 kcmil aluminum |
Computed from Table 310.16 at 75°C and Table 250.66. Check the code edition your state has adopted.
Worked examples
A 200 amp residential service has 2/0 copper ungrounded conductors and the GEC goes to a water pipe. The 2/0 or 3/0 row gives 4 AWG copper. A 400 amp commercial service with two parallel sets of 250 kcmil copper totals 500 kcmil, which falls in the over 350 through 600 row and gives 1/0 AWG copper. An 800 amp service with two sets of 600 kcmil totals 1200 kcmil, above 1100, so it needs 3/0 copper. Run a single wire from that service to a driven rod and 6 AWG copper is enough.
Transformers and separately derived systems
The same table sizes the GEC for a separately derived system such as a dry type transformer secondary. The input is the largest ungrounded conductor of the derived system. If a transformer secondary runs 4/0 copper, the GEC is 2 AWG copper. Find the secondary current for any kVA and voltage with our transformer sizing calculator.
GEC is not the equipment grounding conductor
The GEC ties the system to earth and is sized from the conductor size in Table 250.66. The equipment grounding conductor, or EGC, rides with the circuit conductors and is sized in Table 250.122 from the rating of the breaker or fuse protecting that circuit. Mixing the two tables up is the most common error on ground wire charts. A 200 amp breaker sets the EGC and the service conductor size sets the GEC.
Why substations and plants use bigger wire than the code asks for
Industrial facilities often install 4/0 copper to every electrode even though the table allows 6 AWG at a rod. One engineering reference notes that IEEE 80 usually prefers 2/0 stranded copper in the field for mechanical strength, even where a fault current calculation would allow 4 AWG. That is a design choice, not a code minimum, and anything larger than the table is allowed.
Common questions
What size ground wire for a 200 amp service
For 3/0 copper or 250 kcmil aluminum service conductors the GEC is 4 AWG copper or 2 AWG aluminum under Table 250.66. If the wire only runs to a driven rod, 6 AWG copper is enough.
What size ground wire for a 100 amp service
With 3 AWG copper service conductors the table gives 8 AWG copper, or 6 AWG aluminum. A rod connection can use 6 AWG copper regardless.
What size grounding electrode conductor for a 400 amp service
A single set of 600 kcmil copper conductors falls in the over 350 through 600 kcmil row, so the GEC is 1/0 copper or 3/0 aluminum. A rod connection is still capped at 6 AWG copper.
What is the largest grounding electrode conductor the NEC requires
Table 250.66 stops at 3/0 AWG copper or 250 kcmil aluminum, even for very large services.
What size wire goes to a ground rod
No larger than 6 AWG copper or 4 AWG aluminum under 250.66(A), unless another electrode needing a larger conductor is connected to the same run.
What size conductor goes to a Ufer ground
No larger than 4 AWG copper under 250.66(B). Aluminum is not permitted for that connection.
Is the grounding electrode conductor sized from the breaker
No. Table 250.66 uses the size of the largest ungrounded service conductor. The equipment grounding conductor is the one sized from the breaker rating.
Related pages
Sources
- Open Exam Prep, GEC sizing and installation, complete Table 250.66
- EE Power, NEC 2023 basics grounding and bonding part 14
- IAEI Magazine, sizing of conductors related to grounding and bonding
- Industrial Monitor Direct, NEC 250.66 grounding electrode conductor sizing explained
- Electricity Forum, NEC 250.122 grounding conductor size rules
Free to cite with a link to this page. Always check the edition of the code your inspector enforces.