Breaker size for 300 kVA transformer

A 300 kVA three phase transformer on a 480 V primary draws 361 amps, so the primary breaker is 500 amps when only the primary is protected, and 800 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 833 amps and takes a breaker of 1200 amps at most. Updated 25 November 2026.

Updated November 25, 2026

300 kVA transformer full load current, breaker and wire size

One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.

VoltageFull load ampsBreaker, 125 percentCopper, 75 CAluminum, 75 C
208 V three phase833 A1200 AParallel setsParallel sets
240 V three phase722 A1000 AParallel setsParallel sets
480 V three phase361 A500 A900 kcmil1500 kcmil
600 V three phase289 A400 A600 kcmil900 kcmil

Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.

Breaker size for a 300 kVA transformer, primary and secondary

NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).

Primary voltagePrimary full loadPrimary only, up toWith secondary breaker, primary up to
208 V833 A1200 A2000 A, not above 2,082 A
240 V722 A1000 A1600 A, not above 1,804 A
480 V361 A500 A800 A, not above 902 A
600 V289 A400 A700 A, not above 722 A

A 480 to 208Y/120 volt 300 kVA unit therefore takes a 500 amp primary breaker alone, or up to a 800 amp primary with a 1200 amp breaker on the secondary. Any standard size between those two limits is allowed.

Wire size and ground size for a 300 kVA transformer

Wire size follows the breaker. On a 480 V primary that is 900 kcmil copper or 1500 kcmil aluminum at 500 amps. On the 208 V secondary it is parallel sets of conductors in copper or aluminum, because no single conductor carries that current at 1200 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With parallel sets on the secondary, add the copper area of all the sets in a phase and read the chart for that combined size, and with 900 kcmil on the primary it is 8 AWG copper. The full table is on the grounding electrode conductor size chart.

Fuse size for a 300 kVA transformer

On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 500 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.

Medium voltage primaryFull load amps, 300 kVA three phase
12,470 V13.9 A
13,200 V13.1 A

That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.

Single phase 300 kVA transformer, breaker and amps

Single phase voltageFull load ampsBreaker, 125 percent
240 V1,250 A1600 A
480 V625 A800 A

Single phase current is kVA times 1000 divided by the voltage, no root three.

Worked example, 480 V to 208Y/120 V

A shop needs a 300 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 300 times 1000 divided by 480 times 1.732, which is 361 amps. Times 1.25 is 451 amps, so the next standard breaker is 500 amps with 900 kcmil copper. Secondary current is 833 amps, times 1.25 is 1,041 amps, so the secondary breaker is 1200 amps and the conductors are parallel sets of conductors in copper or aluminum, because no single conductor carries that current. The 1200 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.

Where the 300 kVA unit comes from

A 300 kVA unit is listed with the standard pad mounted sizes, the standard pad mounted sizes with their dimensions and weights are on the pad mounted transformer by kVA pages and the transformer sizes page. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.

Get a 300 kVA transformer quoted

Questions

What size breaker for a 300 kVA transformer?

On a three phase 480 V primary the full load current is 361 amps, so a primary breaker of 500 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 833 amps and the largest secondary breaker is 1200 amps.

What size wire for a 300 kVA transformer?

For the 500 amp primary breaker, 900 kcmil copper or 1500 kcmil aluminum from the 75 C column of NEC Table 310.16. For the 1200 amp secondary breaker, parallel sets of conductors in copper or aluminum, because no single conductor carries that current.

What size fuse for a 300 kVA transformer?

A dry type unit on a 480 V primary uses the same limits as a breaker, up to 500 amps for primary only protection. A 300 kVA pad mount on 12470 volts draws only 13.9 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.

How many amps does a 300 kVA transformer draw?

361 amps at 480 V three phase, 833 amps at 208 V, 722 amps at 240 V and 289 amps at 600 V. Single phase it is 1,250 amps at 240 V.

What size breaker for a 300 kVA transformer 480 to 240 volts single phase?

A single phase 300 kVA transformer from 480 V to 240 V draws 625 amps on the 480 V primary, so a primary breaker of 800 amps is the usual size when only the primary is protected. The 240 V secondary carries 1,250 amps, with a largest secondary breaker of 1600 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).

What is the primary and secondary current of a 300 kVA transformer?

For 480 to 208Y/120 volts, 361 amps on the primary and 833 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.