Padmount Supply

Home / Transformer sizing / Breaker size for 37.5 kVA transformer

Breaker size for 37.5 kVA transformer

A 37.5 kVA three phase transformer on a 480 V primary draws 45.1 amps, so the primary breaker is 60 amps when only the primary is protected, and 110 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 104 amps and takes a breaker of 150 amps at most. Updated 25 November 2026.

Updated November 25, 2026

37.5 kVA transformer full load current, breaker and wire size

One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.

VoltageFull load ampsBreaker, 125 percentCopper, 75 CAluminum, 75 C
208 V three phase104 A150 A1/0 AWG3/0 AWG
240 V three phase90.2 A125 A1 AWG2/0 AWG
480 V three phase45.1 A60 A6 AWG4 AWG
600 V three phase36.1 A50 A8 AWG6 AWG

Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.

Breaker size for a 37.5 kVA transformer, primary and secondary

NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).

Primary voltagePrimary full loadPrimary only, up toWith secondary breaker, primary up to
208 V104 A150 A250 A, not above 260 A
240 V90.2 A125 A225 A, not above 226 A
480 V45.1 A60 A110 A, not above 113 A
600 V36.1 A50 A90 A, not above 90.2 A

A 480 to 208Y/120 volt 37.5 kVA unit therefore takes a 60 amp primary breaker alone, or up to a 110 amp primary with a 150 amp breaker on the secondary. Any standard size between those two limits is allowed.

Wire size and ground size for a 37.5 kVA transformer

Wire size follows the breaker. On a 480 V primary that is 6 AWG copper or 4 AWG aluminum at 60 amps. On the 208 V secondary it is 1/0 AWG copper or 3/0 AWG aluminum at 150 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With 1/0 AWG copper on the secondary that is 6 AWG copper, and with 6 AWG on the primary it is 8 AWG copper. The full table is on the grounding electrode conductor size chart.

Fuse size for a 37.5 kVA transformer

On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 60 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.

Medium voltage primaryFull load amps, 37.5 kVA three phase
12,470 V1.7 A
13,200 V1.6 A

That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.

Single phase 37.5 kVA transformer, breaker and amps

Single phase voltageFull load ampsBreaker, 125 percent
240 V156 A200 A
480 V78.1 A100 A

Single phase current is kVA times 1000 divided by the voltage, no root three.

Worked example, 480 V to 208Y/120 V

A shop needs a 37.5 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 37.5 times 1000 divided by 480 times 1.732, which is 45.1 amps. Times 1.25 is 56.4 amps, so the next standard breaker is 60 amps with 6 AWG copper. Secondary current is 104 amps, times 1.25 is 130 amps, so the secondary breaker is 150 amps and the conductors are 1/0 AWG copper or 3/0 AWG aluminum. The 150 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.

Where the 37.5 kVA unit comes from

A 37.5 kVA unit is a small rating, the standard pad mounted sizes with their dimensions and weights are on the pad mounted transformer by kVA pages and the transformer sizes page. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.

Get a 37.5 kVA transformer quoted

Questions

What size breaker for a 37.5 kVA transformer?

On a three phase 480 V primary the full load current is 45.1 amps, so a primary breaker of 60 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 104 amps and the largest secondary breaker is 150 amps.

What size wire for a 37.5 kVA transformer?

For the 60 amp primary breaker, 6 AWG copper or 4 AWG aluminum from the 75 C column of NEC Table 310.16. For the 150 amp secondary breaker, 1/0 AWG copper or 3/0 AWG aluminum.

What size fuse for a 37.5 kVA transformer?

A dry type unit on a 480 V primary uses the same limits as a breaker, up to 60 amps for primary only protection. A 37.5 kVA pad mount on 12470 volts draws only 1.7 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.

How many amps does a 37.5 kVA transformer draw?

45.1 amps at 480 V three phase, 104 amps at 208 V, 90.2 amps at 240 V and 36.1 amps at 600 V. Single phase it is 156 amps at 240 V.

What size breaker for a 37.5 kVA transformer 480 to 240 volts single phase?

A single phase 37.5 kVA transformer from 480 V to 240 V draws 78.1 amps on the 480 V primary, so a primary breaker of 100 amps is the usual size when only the primary is protected. The 240 V secondary carries 156 amps, with a largest secondary breaker of 200 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).

What is the primary and secondary current of a 37.5 kVA transformer?

For 480 to 208Y/120 volts, 45.1 amps on the primary and 104 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.

Sources, EC and M, NEC guidelines for transformer and transformer feeder protection, NEC Table 310.16 and Table 250.66 as printed on this site, current figures computed on this site. Padmount Supply LLC. Always confirm with the adopted NEC edition and the local inspector.