Padmount Supply

Home / Transformer sizing / Breaker size for 7.5 kVA transformer

Breaker size for 7.5 kVA transformer

A 7.5 kVA three phase transformer on a 480 V primary draws 9.0 amps, so the primary breaker is 15 amps when only the primary is protected, and 20 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 20.8 amps and takes a breaker of 30 amps at most. Updated 25 November 2026.

Updated November 25, 2026

7.5 kVA transformer full load current, breaker and wire size

One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.

VoltageFull load ampsBreaker, 125 percentCopper, 75 CAluminum, 75 C
208 V three phase20.8 A30 A8 AWG8 AWG
240 V three phase18.0 A25 A8 AWG8 AWG
480 V three phase9.0 A15 A8 AWG8 AWG
600 V three phase7.2 A15 A8 AWG8 AWG

Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.

Breaker size for a 7.5 kVA transformer, primary and secondary

NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).

Primary voltagePrimary full loadPrimary only, up toWith secondary breaker, primary up to
208 V20.8 A30 A50 A, not above 52.0 A
240 V18.0 A25 A45 A, not above 45.1 A
480 V9.0 A15 A20 A, not above 22.6 A
600 V7.2 A15 A15 A, not above 18.0 A

A 480 to 208Y/120 volt 7.5 kVA unit therefore takes a 15 amp primary breaker alone, or up to a 20 amp primary with a 30 amp breaker on the secondary. Any standard size between those two limits is allowed.

Wire size and ground size for a 7.5 kVA transformer

Wire size follows the breaker. On a 480 V primary that is 8 AWG copper or 8 AWG aluminum at 15 amps. On the 208 V secondary it is 8 AWG copper or 8 AWG aluminum at 30 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With 8 AWG copper on the secondary that is 8 AWG copper, and with 8 AWG on the primary it is 8 AWG copper. The full table is on the grounding electrode conductor size chart.

Fuse size for a 7.5 kVA transformer

On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 15 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.

Medium voltage primaryFull load amps, 7.5 kVA three phase
12,470 V0.3 A
13,200 V0.3 A

That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.

Single phase 7.5 kVA transformer, breaker and amps

Single phase voltageFull load ampsBreaker, 125 percent
240 V31.3 A40 A
480 V15.6 A20 A

Single phase current is kVA times 1000 divided by the voltage, no root three.

Worked example, 480 V to 208Y/120 V

A shop needs a 7.5 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 7.5 times 1000 divided by 480 times 1.732, which is 9.0 amps. Times 1.25 is 11.3 amps, so the next standard breaker is 15 amps with 8 AWG copper. Secondary current is 20.8 amps, times 1.25 is 26.0 amps, so the secondary breaker is 30 amps and the conductors are 8 AWG copper or 8 AWG aluminum. The 30 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.

Where the 7.5 kVA unit comes from

A 7.5 kVA unit is a small rating, the standard pad mounted sizes with their dimensions and weights are on the pad mounted transformer by kVA pages and the transformer sizes page. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.

Get a 7.5 kVA transformer quoted

Questions

What size breaker for a 7.5 kVA transformer?

On a three phase 480 V primary the full load current is 9.0 amps, so a primary breaker of 15 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 20.8 amps and the largest secondary breaker is 30 amps.

What size wire for a 7.5 kVA transformer?

For the 15 amp primary breaker, 8 AWG copper or 8 AWG aluminum from the 75 C column of NEC Table 310.16. For the 30 amp secondary breaker, 8 AWG copper or 8 AWG aluminum.

What size fuse for a 7.5 kVA transformer?

A dry type unit on a 480 V primary uses the same limits as a breaker, up to 15 amps for primary only protection. A 7.5 kVA pad mount on 12470 volts draws only 0.3 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.

How many amps does a 7.5 kVA transformer draw?

9.0 amps at 480 V three phase, 20.8 amps at 208 V, 18.0 amps at 240 V and 7.2 amps at 600 V. Single phase it is 31.3 amps at 240 V.

What size breaker for a 7.5 kVA transformer 480 to 240 volts single phase?

A single phase 7.5 kVA transformer from 480 V to 240 V draws 15.6 amps on the 480 V primary, so a primary breaker of 20 amps is the usual size when only the primary is protected. The 240 V secondary carries 31.3 amps, with a largest secondary breaker of 40 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).

What is the primary and secondary current of a 7.5 kVA transformer?

For 480 to 208Y/120 volts, 9.0 amps on the primary and 20.8 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.

Sources, EC and M, NEC guidelines for transformer and transformer feeder protection, NEC Table 310.16 and Table 250.66 as printed on this site, current figures computed on this site. Padmount Supply LLC. Always confirm with the adopted NEC edition and the local inspector.