Padmount Supply

Home / Transformer sizing / Breaker size for 750 kVA transformer

Breaker size for 750 kVA transformer

A 750 kVA three phase transformer on a 480 V primary draws 902 amps, so the primary breaker is 1200 amps when only the primary is protected, and 2000 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 2,082 amps and takes a breaker of 3000 amps at most. Updated 25 November 2026.

Updated November 25, 2026

750 kVA transformer full load current, breaker and wire size

One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.

VoltageFull load ampsBreaker, 125 percentCopper, 75 CAluminum, 75 C
208 V three phase2,082 A3000 AParallel setsParallel sets
240 V three phase1,804 A2500 AParallel setsParallel sets
480 V three phase902 A1200 AParallel setsParallel sets
600 V three phase722 A1000 AParallel setsParallel sets

Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.

Breaker size for a 750 kVA transformer, primary and secondary

NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).

Primary voltagePrimary full loadPrimary only, up toWith secondary breaker, primary up to
208 V2,082 A3000 A5000 A, not above 5,204 A
240 V1,804 A2500 A4000 A, not above 4,511 A
480 V902 A1200 A2000 A, not above 2,255 A
600 V722 A1000 A1600 A, not above 1,804 A

A 480 to 208Y/120 volt 750 kVA unit therefore takes a 1200 amp primary breaker alone, or up to a 2000 amp primary with a 3000 amp breaker on the secondary. Any standard size between those two limits is allowed.

Wire size and ground size for a 750 kVA transformer

Wire size follows the breaker. On a 480 V primary that is parallel sets of conductors in copper or aluminum, because no single conductor carries that current at 1200 amps. On the 208 V secondary it is parallel sets of conductors in copper or aluminum, because no single conductor carries that current at 3000 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With parallel sets on the secondary, add the copper area of all the sets in a phase and read the chart for that combined size, and with parallel sets on the primary the same combined size rule applies. The full table is on the grounding electrode conductor size chart.

Fuse size for a 750 kVA transformer

On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 1200 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.

Medium voltage primaryFull load amps, 750 kVA three phase
12,470 V34.7 A
13,200 V32.8 A

That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.

Single phase 750 kVA transformer, breaker and amps

Single phase voltageFull load ampsBreaker, 125 percent
240 V3,125 A4000 A
480 V1,563 A2000 A

Single phase current is kVA times 1000 divided by the voltage, no root three.

Worked example, 480 V to 208Y/120 V

A shop needs a 750 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 750 times 1000 divided by 480 times 1.732, which is 902 amps. Times 1.25 is 1,128 amps, so the next standard breaker is 1200 amps with parallel sets, two or more conductors per phase copper. Secondary current is 2,082 amps, times 1.25 is 2,602 amps, so the secondary breaker is 3000 amps and the conductors are parallel sets of conductors in copper or aluminum, because no single conductor carries that current. The 3000 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.

Where the 750 kVA unit comes from

A 750 kVA unit is listed with the standard pad mounted sizes, the standard pad mounted sizes with their dimensions and weights are on the pad mounted transformer by kVA pages and the transformer sizes page. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.

Get a 750 kVA transformer quoted

Questions

What size breaker for a 750 kVA transformer?

On a three phase 480 V primary the full load current is 902 amps, so a primary breaker of 1200 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 2,082 amps and the largest secondary breaker is 3000 amps.

What size wire for a 750 kVA transformer?

For the 1200 amp primary breaker, parallel sets of conductors in copper or aluminum, because no single conductor carries that current from the 75 C column of NEC Table 310.16. For the 3000 amp secondary breaker, parallel sets of conductors in copper or aluminum, because no single conductor carries that current.

What size fuse for a 750 kVA transformer?

A dry type unit on a 480 V primary uses the same limits as a breaker, up to 1200 amps for primary only protection. A 750 kVA pad mount on 12470 volts draws only 34.7 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.

How many amps does a 750 kVA transformer draw?

902 amps at 480 V three phase, 2,082 amps at 208 V, 1,804 amps at 240 V and 722 amps at 600 V. Single phase it is 3,125 amps at 240 V.

What size breaker for a 750 kVA transformer 480 to 240 volts single phase?

A single phase 750 kVA transformer from 480 V to 240 V draws 1,563 amps on the 480 V primary, so a primary breaker of 2000 amps is the usual size when only the primary is protected. The 240 V secondary carries 3,125 amps, with a largest secondary breaker of 4000 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).

What is the primary and secondary current of a 750 kVA transformer?

For 480 to 208Y/120 volts, 902 amps on the primary and 2,082 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.

Sources, EC and M, NEC guidelines for transformer and transformer feeder protection, NEC Table 310.16 and Table 250.66 as printed on this site, current figures computed on this site. Padmount Supply LLC. Always confirm with the adopted NEC edition and the local inspector.

CallGet a quote