Padmount Supply

Home / Products / Switchgear / S&C PMH and PME pad mounted gear

S&C PMH and PME pad mounted gear

S&C builds two outdoor pad mounted gear families for underground distribution, PMH and PME. Both are rated for 14.4 kV and 25 kV systems. The main difference is the switching design. This page sets out the ratings S&C publishes and what to send us so we can quote the model or an equal.

Updated November 17, 2026

Request S&C PMH or PME gearOr call 786 220 2801.

PMH versus PME

S&C describes manual PMH gear as fuses with Uni-Rupter interrupters, used for single pole live switching of single phase or three phase load circuits on 14.4 kV or 25 kV distribution systems.

S&C describes manual PME gear as elbow connected encased components with Mini-Rupter switches, used for three pole live switching of three phase circuits.

FamilySwitching design per S&CSystem voltage
PMHFuses with Uni-Rupter interrupters, single pole live switching14.4 kV or 25 kV
PMEElbow connected encased components with Mini-Rupter switches, three pole live switching14.4 kV or 25 kV

Published voltage ratings

S&C's PMH table lists nominal 14.4 and 25 kV, maximum 17.0 and 27 kV, and BIL of 95 and 125 kV. The 27 kV maximum is footnoted as 29 kV for gear furnished with switches only or with electronic power fuses.

ClassNominal kVMaximum kVBIL kV
14.4 kV PMH14.417.095
25 kV PMH2527 (29 with switches only or electronic power fuses)125

Fuse holders and short circuit rating

S&C fuse holders for 14.4 kV PMH models are rated 17 kV maximum and 200 amperes maximum. Holders for 25 kV PMH models are rated 29 kV maximum and 200 amperes maximum. PME holders carry the same 14.4 kV and 25 kV class ratings.

For PME, S&C lists specific 14.4 kV models with a short circuit rating of 25,000 amperes RMS symmetrical and 620 MVA. These include PME-4, PME-5, PME-6, PME-9, PME-11 and PME-12 with Fault Fiter fuse mountings, plus PME-10. Check the specification bulletin for the exact catalog number you need.

Listings

T&D World reports UL listings for 14.4 kV PME and PMH gear and CSA listings for 14.4 kV and 25 kV PMH gear. Ask for the listing that your utility or inspector requires.

Price and availability

S&C bulletins do not carry prices, and we do not print one without a dated source. Used and surplus PMH and PME gear does turn up. Send the model, voltage and fuse or switch configuration and we quote new, remanufactured and equal gear, and say which is which.

What to send for a quote

  • Model, for example PMH-9 or PME-11, or the catalog number off the nameplate
  • System voltage class, 14.4 kV or 25 kV
  • Switch and fuse configuration and number of ways
  • Fault current available at the site
  • New, used or remanufactured
  • Delivery ZIP code and needed by date
Request S&C PMH or PME gearOr call 786 220 2801.

Common questions

What is the difference between S&C PME and PMH

Per S&C, PMH gear uses fuses with Uni-Rupter interrupters for single pole live switching, while PME gear uses elbow connected encased components with Mini-Rupter switches for three pole live switching.

What voltage is S&C PMH gear rated for

S&C lists 14.4 kV and 25 kV nominal, 17.0 and 27 kV maximum, with BIL of 95 and 125 kV.

What is the short circuit rating of PME gear

S&C lists 25,000 amperes RMS symmetrical and 620 MVA for specific 14.4 kV PME models such as PME-4, PME-5, PME-6, PME-9, PME-11, PME-12 and PME-10.

How much does S&C pad mounted gear cost

S&C bulletins show no prices. Request a quote with the model and voltage.

Related pages

Sources

Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.

CallGet a quote