A 1200 amp switchboard is the common main distribution point for a 1000 kVA transformer at 480 V, which delivers about 1,203 A at full load. It is built to UL 891 with a molded case or insulated case main. We source new, new surplus and reconditioned units and quote them delivered.
Updated November 17, 2026
Match the switchboard to the transformer
Full load amps are kVA times 1,000 divided by the square root of 3 times volts. A 1200 A bus covers transformers up to about 998 kVA at 480 V before any growth margin. Check any other size with the kVA to amps calculator.
| Transformer | Full load current |
|---|---|
| 750 kVA at 480 V | 902 A |
| 1,000 kVA at 480 V | 1,203 A |
| 1,250 kVA at 480 V | 1,504 A |
| 1,500 kVA at 480 V | 1,804 A |
| 300 kVA at 208 V | 833 A |
| 500 kVA at 208 V | 1,388 A |
Computed from the three phase formula, not read from a source. The service rating you need also depends on code and utility rules.
Main device options
A 1200 A main is either a molded case breaker, an insulated case breaker or a fusible switch. Schneider lists its PowerPact P frame molded case breakers from 100 to 1200 A, so 1200 A is the top of that family. Eaton lists Magnum SB insulated case frames at 800, 1200, 1600, 2000, 2500 and 3000 A. ABB Power Break II insulated case breakers run from 200 to 4000 A.
Molded case mains cost less and fit smaller sections. Insulated case and power breakers carry adjustable trip units, drawout options and higher short circuit ratings. Our main breaker page covers the choice.
Published prices
Prices change by voltage, breaker count and condition. Public examples read in November 2026 are below. They are asking prices, not ours.
| Listing | Asking price |
|---|---|
| Used Square D QED 1200 A switchboard with NAL361200 main breaker, 12 breaker locations, two panels missing | $9,500 |
| Square D 1200 A QED I-Line switchgear, 208/120 V, 78 circuits | $17,500 |
| New Square D QED-2 switchboard, 208Y/120 V, 1200 A to 2500 A, sold out | $140,000 sale, $190,000 regular |
The last row covers a 1200 A to 2500 A range, so it is not a 1200 A price. A partial used unit and a fully built new one are not comparable.
New or reconditioned
Reconditioned units ship far sooner than new builds and match existing lineups. Ask for the test report and warranty terms, which our used switchgear page explains. For new gear, see the lead time page.
What to send for a quote
- System voltage, for example 480Y/277 V three phase four wire
- Main bus amps and the short circuit rating in kA
- Main device, breaker or fusible switch, and the feeder schedule
- Indoor NEMA 1 or outdoor NEMA 3R, and service entrance or not
- New, new surplus or reconditioned, and the date you need it on site
- A photo of the nameplate if you are matching an existing lineup
- Delivery ZIP code
Common questions
What size transformer needs a 1200 amp switchboard
At 480 V, a 1000 kVA transformer draws about 1,203 A, so a 1200 A main is slightly under full load. Many designs use a 1200 A bus for 750 to 1000 kVA depending on loading and code margin.
Who makes 1200 amp switchboards
Square D with QED and Power-Style, Eaton with Pow-R-Line C, Siemens with SB1 and SB2, and GE and ABB on the used market.
How much does a 1200 amp switchboard cost
Public used listings we read ranged from $9,500 for a partial unit to $17,500 for a 208/120 V I-Line lineup. New cost depends on configuration, and we quote delivered.
Is a 1200 amp switchboard the same as switchgear
No. A switchboard is built to UL 891. Low voltage switchgear is built to UL 1558 with drawout power breakers. Our comparison page explains the difference.
Related pages
Sources
- Equipt, used Square D QED 1200 amp switchboard
- Electrical Power and Control, Square D 1200A QED I-Line switchgear
- Electrical Trader, new Square D QED-2 switchboard 1200A to 2500A
- Schneider Electric, PowerPact P-frame molded case circuit breakers
- Eaton, Magnum SB, Magnum DS and Magnum IEC technical product manual
- ABB, Power Break II insulated case circuit breakers
Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.