Electrical service size chart, how many kW is a 200 amp service
A 200 amp, 240 volt single phase service can deliver 48 kVA, which is 48 kW at unity power factor. That is amps times volts divided by 1000. A 100 amp service is 24 kVA, a 400 amp service is 96 kVA, and the same 200 amps on a 480 volt three phase service is 166 kVA. The tables below work out every common service size so you can read kW or kVA straight off the row.
Updated November 16, 2026
Single phase 120/240 volt service, 60 to 600 amps
Kilovolt amps equal amps times 240 divided by 1000 for the two hot legs of a 120/240 volt service. The 80 percent column shows the figure if you hold the load to 80 percent of the service rating, a common design margin for loads that run for hours. Each hot leg alone is 120 volts, so a single 120 volt leg carries half of the full kVA.
| Service amps | kVA at 240 V | kVA at 80 percent | kVA on one 120 V leg |
|---|---|---|---|
| 60 | 14.4 | 11.5 | 7.2 |
| 100 | 24.0 | 19.2 | 12.0 |
| 125 | 30.0 | 24.0 | 15.0 |
| 150 | 36.0 | 28.8 | 18.0 |
| 200 | 48.0 | 38.4 | 24.0 |
| 225 | 54.0 | 43.2 | 27.0 |
| 300 | 72.0 | 57.6 | 36.0 |
| 400 | 96.0 | 76.8 | 48.0 |
| 600 | 144.0 | 115.2 | 72.0 |
Computed, kVA = amps x volts / 1000. kW equals kVA times power factor, so kW and kVA match only at a power factor of 1.0.
Three phase service, 125 to 1200 amps
Three phase kVA equals amps times line to line volts times the square root of 3 divided by 1000. The 480 volt column also shows the 80 percent figure.
| Service amps | kVA at 208 V | kVA at 240 V | kVA at 480 V | 480 V at 80 percent |
|---|---|---|---|---|
| 125 | 45.0 | 52.0 | 103.9 | 83.1 |
| 150 | 54.0 | 62.4 | 124.7 | 99.8 |
| 200 | 72.1 | 83.1 | 166.3 | 133.0 |
| 225 | 81.1 | 93.5 | 187.1 | 149.6 |
| 300 | 108.1 | 124.7 | 249.4 | 199.5 |
| 400 | 144.1 | 166.3 | 332.6 | 266.0 |
| 600 | 216.2 | 249.4 | 498.8 | 399.1 |
| 800 | 288.2 | 332.6 | 665.1 | 532.1 |
| 1000 | 360.3 | 415.7 | 831.4 | 665.1 |
| 1200 | 432.3 | 498.8 | 997.7 | 798.1 |
Computed, kVA = amps x volts x 1.732 / 1000.
kW versus kVA
A service is rated in amps, and amps times volts gives kVA. Real power in kW is kVA times power factor. Resistive heat has a power factor near 1.0, motors and lighting ballasts run lower. So a 200 amp, 240 volt service is 48 kVA, and the kW it delivers depends on what is plugged in. The same arithmetic shows up when a home load is converted to amps, for example a 41,550 watt calculated load at 240 volts is 173.1 amps.
What transformer sits behind the service
A single home on a 200 amp service is normally one of several homes sharing a pole or pad mount transformer, so the utility sizes the transformer for the group and not for the service rating. Larger three phase services of 400 amps and more at 208 or 480 volts are fed from their own transformer. For the transformer sizes that match 400 to 4000 amp commercial services see the commercial service size chart.
How to read the numbers
These are service ratings, not loads. The actual connected load is set by the load calculation for the building, and the calculated demand is usually well below the service rating. Use the chart to check that a planned load fits a service or to find the service size for a known kVA, then confirm with a load calculation and the local utility.
Common questions
How many kW is a 200 amp service
At 240 volts single phase a 200 amp service is 48 kVA, or 48 kW at a power factor of 1.0. At 80 percent loading it is 38.4 kVA.
How many kW is a 100 amp service
A 100 amp, 240 volt single phase service is 24 kVA, or 24 kW at a power factor of 1.0. At 80 percent loading it is 19.2 kVA.
How many kW is a 400 amp service
A 400 amp, 240 volt single phase service is 96 kVA. A 400 amp, 480 volt three phase service is 332 kVA.
How do you convert service amps to kVA
Single phase kVA is amps times volts divided by 1000. Three phase kVA is amps times line to line volts times 1.732 divided by 1000.
Is kVA the same as kW
Only at a power factor of 1.0. kW is kVA times the power factor of the load.