Breaker size for 100 kVA transformer

A 100 kVA three phase transformer on a 480 V primary draws 120 amps, so the primary breaker is 175 amps when only the primary is protected, and 300 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 278 amps and takes a breaker of 350 amps at most. Updated 25 November 2026.

Updated November 25, 2026

100 kVA transformer full load current, breaker and wire size

One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.

VoltageFull load ampsBreaker, 125 percentCopper, 75 CAluminum, 75 C
208 V three phase278 A350 A500 kcmil700 kcmil
240 V three phase241 A350 A500 kcmil700 kcmil
480 V three phase120 A175 A2/0 AWG4/0 AWG
600 V three phase96.2 A125 A1 AWG2/0 AWG

Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.

Breaker size for a 100 kVA transformer, primary and secondary

NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).

Primary voltagePrimary full loadPrimary only, up toWith secondary breaker, primary up to
208 V278 A350 A600 A, not above 694 A
240 V241 A350 A600 A, not above 601 A
480 V120 A175 A300 A, not above 301 A
600 V96.2 A125 A225 A, not above 241 A

A 480 to 208Y/120 volt 100 kVA unit therefore takes a 175 amp primary breaker alone, or up to a 300 amp primary with a 350 amp breaker on the secondary. Any standard size between those two limits is allowed.

Wire size and ground size for a 100 kVA transformer

Wire size follows the breaker. On a 480 V primary that is 2/0 AWG copper or 4/0 AWG aluminum at 175 amps. On the 208 V secondary it is 500 kcmil copper or 700 kcmil aluminum at 350 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With 500 kcmil copper on the secondary that is 1/0 AWG copper, and with 2/0 AWG on the primary it is 4 AWG copper. The full table is on the grounding electrode conductor size chart.

Fuse size for a 100 kVA transformer

On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 175 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.

Medium voltage primaryFull load amps, 100 kVA three phase
12,470 V4.6 A
13,200 V4.4 A

That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.

Single phase 100 kVA transformer, breaker and amps

Single phase voltageFull load ampsBreaker, 125 percent
240 V417 A600 A
480 V208 A300 A

Single phase current is kVA times 1000 divided by the voltage, no root three.

100 kVA single phase pad mount, the utility side

100 kVA is also a standard single phase pad mounted rating, listed here at 7200 or 12470 GrdY volts primary and 120/240 volts secondary, about 36 x 38 x 44 inches and 950 pounds with fluid, at 2.5 percent impedance. Its secondary full load current is 417 amps at 240 volts, and the secondary breaker limit is 600 amps. Typical use, eight to twelve houses, a small apartment building, a fast food unit. See the 100 kVA single phase pad mounted transformer.

Single phase primaryFull load amps, 100 kVA
7,200 V13.9 A
7,620 V13.1 A
14,400 V6.9 A

On a 100 kVA three phase unit the same kVA is split across three lines, so the 480 volt primary draws 120 amps, against 208 amps for a single phase unit at 480 volts. Next up in three phase, see the 112.5 kVA page, 100 kVA is not a standard three phase pad mount rating, and the step below is the 75 kVA page.

Worked example, 480 V to 208Y/120 V

A shop needs a 100 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 100 times 1000 divided by 480 times 1.732, which is 120 amps. Times 1.25 is 150 amps, so the next standard breaker is 175 amps with 2/0 AWG copper. Secondary current is 278 amps, times 1.25 is 347 amps, so the secondary breaker is 350 amps and the conductors are 500 kcmil copper or 700 kcmil aluminum. The 350 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.

Where the 100 kVA unit comes from

A 100 kVA unit is listed with the standard pad mounted sizes, the standard pad mounted sizes with their dimensions and weights are on the pad mounted transformer by kVA pages and the transformer sizes page. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.

Get a 100 kVA transformer quoted

Questions

What size breaker for a 100 kVA transformer?

On a three phase 480 V primary the full load current is 120 amps, so a primary breaker of 175 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 278 amps and the largest secondary breaker is 350 amps.

What size wire for a 100 kVA transformer?

For the 175 amp primary breaker, 2/0 AWG copper or 4/0 AWG aluminum from the 75 C column of NEC Table 310.16. For the 350 amp secondary breaker, 500 kcmil copper or 700 kcmil aluminum.

What size fuse for a 100 kVA transformer?

A dry type unit on a 480 V primary uses the same limits as a breaker, up to 175 amps for primary only protection. A 100 kVA pad mount on 12470 volts draws only 4.6 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.

How many amps does a 100 kVA transformer draw?

120 amps at 480 V three phase, 278 amps at 208 V, 241 amps at 240 V and 96.2 amps at 600 V. Single phase it is 417 amps at 240 V.

What size breaker for a 100 kVA transformer 480 to 240 volts single phase?

A single phase 100 kVA transformer from 480 V to 240 V draws 208 amps on the 480 V primary, so a primary breaker of 300 amps is the usual size when only the primary is protected. The 240 V secondary carries 417 amps, with a largest secondary breaker of 600 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).

What is the primary and secondary current of a 100 kVA transformer?

For 480 to 208Y/120 volts, 120 amps on the primary and 278 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.