Breaker size for 75 kVA transformer
A 75 kVA three phase transformer on a 480 V primary draws 90.2 amps, so the primary breaker is 125 amps when only the primary is protected, and 225 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 208 amps and takes a breaker of 300 amps at most. Updated 25 November 2026.
Updated November 25, 2026
75 kVA transformer full load current, breaker and wire size
One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.
| Voltage | Full load amps | Breaker, 125 percent | Copper, 75 C | Aluminum, 75 C |
|---|---|---|---|---|
| 208 V three phase | 208 A | 300 A | 350 kcmil | 500 kcmil |
| 240 V three phase | 180 A | 250 A | 250 kcmil | 350 kcmil |
| 480 V three phase | 90.2 A | 125 A | 1 AWG | 2/0 AWG |
| 600 V three phase | 72.2 A | 100 A | 3 AWG | 1 AWG |
Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.
Breaker size for a 75 kVA transformer, primary and secondary
NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).
| Primary voltage | Primary full load | Primary only, up to | With secondary breaker, primary up to |
|---|---|---|---|
| 208 V | 208 A | 300 A | 500 A, not above 520 A |
| 240 V | 180 A | 250 A | 450 A, not above 451 A |
| 480 V | 90.2 A | 125 A | 225 A, not above 226 A |
| 600 V | 72.2 A | 100 A | 175 A, not above 180 A |
A 480 to 208Y/120 volt 75 kVA unit therefore takes a 125 amp primary breaker alone, or up to a 225 amp primary with a 300 amp breaker on the secondary. Any standard size between those two limits is allowed.
Wire size and ground size for a 75 kVA transformer
Wire size follows the breaker. On a 480 V primary that is 1 AWG copper or 2/0 AWG aluminum at 125 amps. On the 208 V secondary it is 350 kcmil copper or 500 kcmil aluminum at 300 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With 350 kcmil copper on the secondary that is 2 AWG copper, and with 1 AWG on the primary it is 6 AWG copper. The full table is on the grounding electrode conductor size chart.
Fuse size for a 75 kVA transformer
On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 125 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.
| Medium voltage primary | Full load amps, 75 kVA three phase |
|---|---|
| 12,470 V | 3.5 A |
| 13,200 V | 3.3 A |
That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.
Single phase 75 kVA transformer, breaker and amps
| Single phase voltage | Full load amps | Breaker, 125 percent |
|---|---|---|
| 240 V | 313 A | 400 A |
| 480 V | 156 A | 200 A |
Single phase current is kVA times 1000 divided by the voltage, no root three.
Worked example, 480 V to 208Y/120 V
A shop needs a 75 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 75 times 1000 divided by 480 times 1.732, which is 90.2 amps. Times 1.25 is 113 amps, so the next standard breaker is 125 amps with 1 AWG copper. Secondary current is 208 amps, times 1.25 is 260 amps, so the secondary breaker is 300 amps and the conductors are 350 kcmil copper or 500 kcmil aluminum. The 300 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.
Where the 75 kVA unit comes from
Indoors, a dry type unit, see the 75 kVA dry type transformer. Outdoors on a pad, the 75 kVA pad mounted transformer, with its dimensions, weight and prices. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.
Get a 75 kVA transformer quoted
Questions
What size breaker for a 75 kVA transformer?
On a three phase 480 V primary the full load current is 90.2 amps, so a primary breaker of 125 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 208 amps and the largest secondary breaker is 300 amps.
What size wire for a 75 kVA transformer?
For the 125 amp primary breaker, 1 AWG copper or 2/0 AWG aluminum from the 75 C column of NEC Table 310.16. For the 300 amp secondary breaker, 350 kcmil copper or 500 kcmil aluminum.
What size fuse for a 75 kVA transformer?
A dry type unit on a 480 V primary uses the same limits as a breaker, up to 125 amps for primary only protection. A 75 kVA pad mount on 12470 volts draws only 3.5 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.
How many amps does a 75 kVA transformer draw?
90.2 amps at 480 V three phase, 208 amps at 208 V, 180 amps at 240 V and 72.2 amps at 600 V. Single phase it is 313 amps at 240 V.
What size breaker for a 75 kVA transformer 480 to 240 volts single phase?
A single phase 75 kVA transformer from 480 V to 240 V draws 156 amps on the 480 V primary, so a primary breaker of 200 amps is the usual size when only the primary is protected. The 240 V secondary carries 313 amps, with a largest secondary breaker of 400 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).
What is the primary and secondary current of a 75 kVA transformer?
For 480 to 208Y/120 volts, 90.2 amps on the primary and 208 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.