Breaker size for 225 kVA transformer
A 225 kVA three phase transformer on a 480 V primary draws 271 amps, so the primary breaker is 350 amps when only the primary is protected, and 600 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 625 amps and takes a breaker of 800 amps at most. Updated 25 November 2026.
Updated November 25, 2026
225 kVA transformer full load current, breaker and wire size
One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.
| Voltage | Full load amps | Breaker, 125 percent | Copper, 75 C | Aluminum, 75 C |
|---|---|---|---|---|
| 208 V three phase | 625 A | 800 A | Parallel sets | Parallel sets |
| 240 V three phase | 541 A | 700 A | Parallel sets | Parallel sets |
| 480 V three phase | 271 A | 350 A | 500 kcmil | 700 kcmil |
| 600 V three phase | 217 A | 300 A | 350 kcmil | 500 kcmil |
Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.
Breaker size for a 225 kVA transformer, primary and secondary
NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).
| Primary voltage | Primary full load | Primary only, up to | With secondary breaker, primary up to |
|---|---|---|---|
| 208 V | 625 A | 800 A | 1200 A, not above 1,561 A |
| 240 V | 541 A | 700 A | 1200 A, not above 1,353 A |
| 480 V | 271 A | 350 A | 600 A, not above 677 A |
| 600 V | 217 A | 300 A | 500 A, not above 541 A |
A 480 to 208Y/120 volt 225 kVA unit therefore takes a 350 amp primary breaker alone, or up to a 600 amp primary with a 800 amp breaker on the secondary. Any standard size between those two limits is allowed.
Wire size and ground size for a 225 kVA transformer
Wire size follows the breaker. On a 480 V primary that is 500 kcmil copper or 700 kcmil aluminum at 350 amps. On the 208 V secondary it is parallel sets of conductors in copper or aluminum, because no single conductor carries that current at 800 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With parallel sets on the secondary, add the copper area of all the sets in a phase and read the chart for that combined size, and with 500 kcmil on the primary it is 1/0 AWG copper. The full table is on the grounding electrode conductor size chart.
Fuse size for a 225 kVA transformer
On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 350 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.
| Medium voltage primary | Full load amps, 225 kVA three phase |
|---|---|
| 12,470 V | 10.4 A |
| 13,200 V | 9.8 A |
That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.
Single phase 225 kVA transformer, breaker and amps
| Single phase voltage | Full load amps | Breaker, 125 percent |
|---|---|---|
| 240 V | 938 A | 1200 A |
| 480 V | 469 A | 600 A |
Single phase current is kVA times 1000 divided by the voltage, no root three.
Worked example, 480 V to 208Y/120 V
A shop needs a 225 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 225 times 1000 divided by 480 times 1.732, which is 271 amps. Times 1.25 is 338 amps, so the next standard breaker is 350 amps with 500 kcmil copper. Secondary current is 625 amps, times 1.25 is 781 amps, so the secondary breaker is 800 amps and the conductors are parallel sets of conductors in copper or aluminum, because no single conductor carries that current. The 800 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.
Where the 225 kVA unit comes from
Indoors, a dry type unit, see the 225 kVA dry type transformer. Outdoors on a pad, the 225 kVA pad mounted transformer, with its dimensions, weight and prices. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.
Get a 225 kVA transformer quoted
Questions
What size breaker for a 225 kVA transformer?
On a three phase 480 V primary the full load current is 271 amps, so a primary breaker of 350 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 625 amps and the largest secondary breaker is 800 amps.
What size wire for a 225 kVA transformer?
For the 350 amp primary breaker, 500 kcmil copper or 700 kcmil aluminum from the 75 C column of NEC Table 310.16. For the 800 amp secondary breaker, parallel sets of conductors in copper or aluminum, because no single conductor carries that current.
What size fuse for a 225 kVA transformer?
A dry type unit on a 480 V primary uses the same limits as a breaker, up to 350 amps for primary only protection. A 225 kVA pad mount on 12470 volts draws only 10.4 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.
How many amps does a 225 kVA transformer draw?
271 amps at 480 V three phase, 625 amps at 208 V, 541 amps at 240 V and 217 amps at 600 V. Single phase it is 938 amps at 240 V.
What size breaker for a 225 kVA transformer 480 to 240 volts single phase?
A single phase 225 kVA transformer from 480 V to 240 V draws 469 amps on the 480 V primary, so a primary breaker of 600 amps is the usual size when only the primary is protected. The 240 V secondary carries 938 amps, with a largest secondary breaker of 1200 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).
What is the primary and secondary current of a 225 kVA transformer?
For 480 to 208Y/120 volts, 271 amps on the primary and 625 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.