Breaker size for 50 kVA transformer

A 50 kVA three phase transformer on a 480 V primary draws 60.1 amps, so the primary breaker is 80 amps when only the primary is protected, and 150 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 139 amps and takes a breaker of 175 amps at most. Updated 25 November 2026.

Updated November 25, 2026

50 kVA transformer full load current, breaker and wire size

One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.

VoltageFull load ampsBreaker, 125 percentCopper, 75 CAluminum, 75 C
208 V three phase139 A175 A2/0 AWG4/0 AWG
240 V three phase120 A175 A2/0 AWG4/0 AWG
480 V three phase60.1 A80 A4 AWG2 AWG
600 V three phase48.1 A70 A4 AWG3 AWG

Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.

Breaker size for a 50 kVA transformer, primary and secondary

NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).

Primary voltagePrimary full loadPrimary only, up toWith secondary breaker, primary up to
208 V139 A175 A300 A, not above 347 A
240 V120 A175 A300 A, not above 301 A
480 V60.1 A80 A150 A, not above 150 A
600 V48.1 A70 A110 A, not above 120 A

A 480 to 208Y/120 volt 50 kVA unit therefore takes a 80 amp primary breaker alone, or up to a 150 amp primary with a 175 amp breaker on the secondary. Any standard size between those two limits is allowed.

Wire size and ground size for a 50 kVA transformer

Wire size follows the breaker. On a 480 V primary that is 4 AWG copper or 2 AWG aluminum at 80 amps. On the 208 V secondary it is 2/0 AWG copper or 4/0 AWG aluminum at 175 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With 2/0 AWG copper on the secondary that is 4 AWG copper, and with 4 AWG on the primary it is 8 AWG copper. The full table is on the grounding electrode conductor size chart.

Fuse size for a 50 kVA transformer

On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 80 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.

Medium voltage primaryFull load amps, 50 kVA three phase
12,470 V2.3 A
13,200 V2.2 A

That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.

Single phase 50 kVA transformer, breaker and amps

Single phase voltageFull load ampsBreaker, 125 percent
240 V208 A300 A
480 V104 A150 A

Single phase current is kVA times 1000 divided by the voltage, no root three.

50 kVA single phase pad mount, the utility side

50 kVA is also a standard single phase pad mounted rating, listed here at 7200 or 12470 GrdY volts primary and 120/240 volts secondary, about 32 x 34 x 40 inches and 610 pounds with fluid, at 2.3 percent impedance. Its secondary full load current is 208 amps at 240 volts, and the secondary breaker limit is 300 amps. Typical use, three to five houses, a small commercial unit, a irrigation pump. See the 50 kVA single phase pad mounted transformer.

Single phase primaryFull load amps, 50 kVA
7,200 V6.9 A
7,620 V6.6 A
14,400 V3.5 A

On a 50 kVA three phase unit the same kVA is split across three lines, so the 480 volt primary draws 60.1 amps, against 104 amps for a single phase unit at 480 volts. Between 45 and 75 kVA three phase, see the 45 kVA and 75 kVA pages, 50 kVA is not a standard three phase pad mount rating.

Worked example, 480 V to 208Y/120 V

A shop needs a 50 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 50 times 1000 divided by 480 times 1.732, which is 60.1 amps. Times 1.25 is 75.2 amps, so the next standard breaker is 80 amps with 4 AWG copper. Secondary current is 139 amps, times 1.25 is 173 amps, so the secondary breaker is 175 amps and the conductors are 2/0 AWG copper or 4/0 AWG aluminum. The 175 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.

Where the 50 kVA unit comes from

A 50 kVA unit is a small rating, the standard pad mounted sizes with their dimensions and weights are on the pad mounted transformer by kVA pages and the transformer sizes page. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.

Get a 50 kVA transformer quoted

Questions

What size breaker for a 50 kVA transformer?

On a three phase 480 V primary the full load current is 60.1 amps, so a primary breaker of 80 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 139 amps and the largest secondary breaker is 175 amps.

What size wire for a 50 kVA transformer?

For the 80 amp primary breaker, 4 AWG copper or 2 AWG aluminum from the 75 C column of NEC Table 310.16. For the 175 amp secondary breaker, 2/0 AWG copper or 4/0 AWG aluminum.

What size fuse for a 50 kVA transformer?

A dry type unit on a 480 V primary uses the same limits as a breaker, up to 80 amps for primary only protection. A 50 kVA pad mount on 12470 volts draws only 2.3 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.

How many amps does a 50 kVA transformer draw?

60.1 amps at 480 V three phase, 139 amps at 208 V, 120 amps at 240 V and 48.1 amps at 600 V. Single phase it is 208 amps at 240 V.

What size breaker for a 50 kVA transformer 480 to 240 volts single phase?

A single phase 50 kVA transformer from 480 V to 240 V draws 104 amps on the 480 V primary, so a primary breaker of 150 amps is the usual size when only the primary is protected. The 240 V secondary carries 208 amps, with a largest secondary breaker of 300 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).

What is the primary and secondary current of a 50 kVA transformer?

For 480 to 208Y/120 volts, 60.1 amps on the primary and 139 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.

Sources, EC and M, NEC guidelines for transformer and transformer feeder protection, NEC Table 310.16 and Table 250.66 as printed on this site, current figures computed on this site. Padmount Supply LLC. Always confirm with the adopted NEC edition and the local inspector.