Padmount Supply

Home / Products / Switchgear / Medium voltage vacuum circuit breakers

Medium voltage vacuum circuit breakers

Medium voltage vacuum breakers sit in metal clad switchgear, usually draw out. Ratings depend on voltage class, continuous current and interrupting current. This page collects figures from maker literature and shows what to send so we match the breaker to your lineup.

Updated November 17, 2026

Request a vacuum breaker quoteOr call 786 220 2801.

Ratings from Eaton VCP-W literature

Eaton's VCP-W breakers are listed from 4.76 kV through 38 kV.

ClassContinuous currentInterrupting rating
5 and 15 kV1200, 2000, 3000 A and 4000 A forced cooledUp to 63 kA
27 kV1200 and 2000 A16, 22, 25 and 40 kA
38 kV1200, 1600 and 2500 A depending on kA rating16, 21, 25, 32 and 40 kA

Other makers

ABB's AMVAC breaker is available for 5, 15 and 27 kV in stationary and draw out forms, tested to ANSI C37.04, C37.06 and C37.09. Siemens SIEBREAK is a fixed mounted 25 kA and 40 kA design for 5 and 15 kV.

Matching a breaker to a lineup

A replacement breaker must fit the cubicle, so give the switchgear maker, type and the breaker nameplate. Eaton notes that some figures in its tables are arc ratings rather than interrupting capacity, so check each one. Eaton's guide also describes a change in the C37.06 rating basis, so confirm which applies.

Price and availability

We print no price without a dated source. New, remanufactured and surplus breakers all exist, and we say which is which in the quote.

What to send for a quote

  • Switchgear maker and type, for example Eaton VCP-W
  • Breaker model and nameplate rating
  • Voltage class and continuous current
  • Interrupting rating in kA
  • Control voltage
  • New, remanufactured or used
  • Delivery ZIP code and needed by date
Request a vacuum breaker quoteOr call 786 220 2801.

Common questions

What ratings do medium voltage vacuum breakers come in

Eaton lists 5 to 15 kV breakers to 63 kA and 3000 A, with 27 kV and 38 kV classes also offered.

What is the difference between draw out and fixed mounted breakers

Draw out breakers roll in and out of the cubicle. Siemens SIEBREAK, for example, is fixed mounted.

Can I swap breakers between makers

Not as a rule. The breaker must match the cubicle, so give the switchgear type and breaker nameplate.

How much does a vacuum circuit breaker cost

Prices vary by class and rating. Request a quote.

Related pages

Sources

Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.

CallGet a quote