Home / Products / Switchgear / 15kV switchgear
15kV switchgear
15 kV class switchgear covers systems up to 15 kV maximum, which includes 13.8 kV and 12.47 kV distribution. Metal clad lineups in this class use draw out vacuum breakers. This page collects the ratings that manufacturers publish and the details a quote needs.
Updated November 17, 2026
Typical 15 kV ratings from manufacturer literature
Metal clad switchgear in the ANSI world is built with main bus ratings of 1200 A, 2000 A and 3000 A. Some 15 kV lineups also offer a 4000 A forced cooled rating. Interrupting ratings vary by maker and breaker frame.
| Item | What the literature says | Source |
|---|---|---|
| Main bus continuous current | 1200 A, 2000 A, 3000 A, plus 4000 A forced cooled on some lineups | Eaton VacClad-W guide |
| Breaker interrupting rating, Eaton | Up to 63 kA at 5 kV and 15 kV | Eaton VacClad-W guide |
| Breaker interrupting rating, ABB ADVAC | 15 kV ratings of 25, 31.5, 40 and 50 kA, with 63 kA on the 5 and 15 kV breakers | ABB ADVAC guide |
| Breaker interrupting rating, Siemens SIEBREAK | 25 kA and 40 kA, fixed mounted, 5 and 15 kV | Siemens SIEBREAK brochure |
A note on MVA ratings
Older 15 kV breakers carry MVA class ratings such as 500 or 1000 MVA. ABB says its ADVAC line is available through 15 kV with interrupting ratings to 1000 MVA. Do not convert between MVA and kA on your own for a purchase. Ask for the nameplate or the maker's ratings table, and note which rating basis it uses, because Eaton's guide describes a change in the C37.06 rating basis.
What to specify
Give the system voltage, the available fault current, the bus current, the number of breaker and feeder units, indoor or outdoor and any arc resistant need. A used lineup needs the manufacturer, type and breaker model.
New, used and lead time
We quote new gear and reconditioned lineups. See the lead time page for planning figures and the used switchgear page for what to check before buying a used breaker. We print no price here without a dated source.
What to send for a quote
- System voltage, for example 13.8 kV or 12.47 kV
- Available fault current in kA
- Main bus current, 1200, 2000 or 3000 A
- Number of breaker and feeder cubicles
- Indoor, outdoor walk in or arc resistant
- New or reconditioned
- Delivery ZIP code and needed by date
Common questions
What bus ratings does 15 kV metal clad switchgear come in
Main bus ratings of 1200 A, 2000 A and 3000 A are standard, and some lineups offer 4000 A forced cooled.
What interrupting rating can a 15 kV vacuum breaker have
Eaton lists up to 63 kA at 15 kV. ABB lists 25, 31.5, 40 and 50 kA with 63 kA on some breakers. Siemens SIEBREAK lists 25 kA and 40 kA.
Is 13.8 kV switchgear 15 kV class
Yes. 13.8 kV systems are served by 15 kV class equipment, which has a 15 kV maximum rating.
How much does 15 kV switchgear cost
Prices vary with bus rating, breaker count and options. See the switchgear prices page and request a quote.
Related pages
Sources
- Eaton, VacClad-W 5 to 15 kV metal clad switchgear design guide
- ABB, ADVAC technical guide
- Siemens, SIEBREAK vacuum circuit breaker for ANSI medium voltage air insulated switchgear
Market figures are public asking prices and published industry figures, dated where the source gives a date. They are not our prices. A quote from us is a delivered price for a specific unit.