Home / Transformer sizing / Breaker size for 167 kVA transformer
Breaker size for 167 kVA transformer
A 167 kVA three phase transformer on a 480 V primary draws 201 amps, so the primary breaker is 300 amps when only the primary is protected, and 500 amps at most when the secondary has its own breaker. On a 208Y/120 secondary it delivers 464 amps and takes a breaker of 600 amps at most. Updated 25 November 2026.
Updated November 25, 2026
167 kVA transformer full load current, breaker and wire size
One row for each common voltage, three phase. Full load amps are kVA times 1000 divided by the voltage times the square root of three. The breaker is 125 percent of full load, next standard size up from NEC 240.6(A). The wire is the smallest single conductor whose 75 C ampacity in NEC Table 310.16 carries that breaker, the same values printed on the wire ampacity chart.
| Voltage | Full load amps | Breaker, 125 percent | Copper, 75 C | Aluminum, 75 C |
|---|---|---|---|---|
| 208 V three phase | 464 A | 600 A | 1500 kcmil | Parallel sets |
| 240 V three phase | 402 A | 600 A | 1500 kcmil | Parallel sets |
| 480 V three phase | 201 A | 300 A | 350 kcmil | 500 kcmil |
| 600 V three phase | 161 A | 225 A | 4/0 AWG | 300 kcmil |
Dry type transformer of 1000 volts or less on both sides. Terminal limits, ambient and more than three conductors in a conduit change the answer, see the breaker size chart and check the adopted code edition.
Breaker size for a 167 kVA transformer, primary and secondary
NEC Table 450.3(B) limits protection on a transformer of 1000 volts or less. With protection on the primary only, the primary device is at most 125 percent of primary full load current, and the next standard size up is allowed. With protection on both sides, the primary can go to 250 percent and the secondary is capped at 125 percent. The 250 percent column exists because a transformer draws a brief inrush when it is energized, so the primary device can be larger when a secondary device already guards against overload (EC and M).
| Primary voltage | Primary full load | Primary only, up to | With secondary breaker, primary up to |
|---|---|---|---|
| 208 V | 464 A | 600 A | 1000 A, not above 1,159 A |
| 240 V | 402 A | 600 A | 1000 A, not above 1,004 A |
| 480 V | 201 A | 300 A | 500 A, not above 502 A |
| 600 V | 161 A | 225 A | 400 A, not above 402 A |
A 480 to 208Y/120 volt 167 kVA unit therefore takes a 300 amp primary breaker alone, or up to a 500 amp primary with a 600 amp breaker on the secondary. Any standard size between those two limits is allowed.
Wire size and ground size for a 167 kVA transformer
Wire size follows the breaker. On a 480 V primary that is 350 kcmil copper or 500 kcmil aluminum at 300 amps. On the 208 V secondary it is 1500 kcmil copper, or parallel sets in aluminum at 600 amps. The grounding electrode conductor is taken from NEC Table 250.66 by the size of the largest ungrounded conductor. With 1500 kcmil copper on the secondary that is 8 AWG copper, and with 350 kcmil on the primary it is 2 AWG copper. The full table is on the grounding electrode conductor size chart.
Fuse size for a 167 kVA transformer
On a primary of 1000 volts or less a fuse follows the same 125 and 250 percent limits as a breaker, so the maximum is 300 amps at 480 V for primary only protection. A transformer fed at medium voltage draws very little current at this size.
| Medium voltage primary | Full load amps, 167 kVA three phase |
|---|---|
| 12,470 V | 7.7 A |
| 13,200 V | 7.3 A |
That current is far below any fuse rating, which is why the protective fuse is chosen from the transformer maker coordination table and not by a percentage. A fuse sized at full load would open on inrush. The transformer fuse size chart explains Bay-O-Net and current limiting pairs, and the utility standard decides which cartridge it uses.
Single phase 167 kVA transformer, breaker and amps
| Single phase voltage | Full load amps | Breaker, 125 percent |
|---|---|---|
| 240 V | 696 A | 1000 A |
| 480 V | 348 A | 450 A |
Single phase current is kVA times 1000 divided by the voltage, no root three.
167 kVA single phase pad mount, the utility side
167 kVA is also a standard single phase pad mounted rating, listed here at 7200 or 12470 GrdY volts primary and 120/240 volts secondary, about 40 x 42 x 48 inches and 1,240 pounds with fluid, at 2.6 percent impedance. Its secondary full load current is 696 amps at 240 volts, and the secondary breaker limit is 1000 amps. Typical use, a large single phase service, a rural commercial load, an agricultural pump station. See the 167 kVA single phase pad mounted transformer.
| Single phase primary | Full load amps, 167 kVA |
|---|---|
| 7,200 V | 23.2 A |
| 7,620 V | 21.9 A |
| 14,400 V | 11.6 A |
On a 167 kVA three phase unit the same kVA is split across three lines, so the 480 volt primary draws 201 amps, against 348 amps for a single phase unit at 480 volts. Three phase units step from 150 to 225 kVA, see the 150 kVA and 225 kVA pages, 167 kVA is a single phase pad mount rating and the three phase figures above are for comparison only.
Worked example, 480 V to 208Y/120 V
A shop needs a 167 kVA dry type transformer from a 480 V panel to a 208Y/120 V sub panel. Primary current is 167 times 1000 divided by 480 times 1.732, which is 201 amps. Times 1.25 is 251 amps, so the next standard breaker is 300 amps with 350 kcmil copper. Secondary current is 464 amps, times 1.25 is 579 amps, so the secondary breaker is 600 amps and the conductors are 1500 kcmil copper, or parallel sets in aluminum. The 600 amp figure is the ceiling, a smaller breaker that still carries the real load is fine.
Where the 167 kVA unit comes from
A 167 kVA unit is listed with the standard pad mounted sizes, the standard pad mounted sizes with their dimensions and weights are on the pad mounted transformer by kVA pages and the transformer sizes page. Amps for any other rating are in the kVA to amps calculator and the transformer sizing calculator. Other families are on the transformer sizing hub. For a larger service, see the 125 kVA transformer sizes and dimensions.
Get a 167 kVA transformer quoted
Questions
What size breaker for a 167 kVA transformer?
On a three phase 480 V primary the full load current is 201 amps, so a primary breaker of 300 amps is the usual size when only the primary is protected. On the 208Y/120 secondary the full load current is 464 amps and the largest secondary breaker is 600 amps.
What size wire for a 167 kVA transformer?
For the 300 amp primary breaker, 350 kcmil copper or 500 kcmil aluminum from the 75 C column of NEC Table 310.16. For the 600 amp secondary breaker, 1500 kcmil copper, or parallel sets in aluminum.
What size fuse for a 167 kVA transformer?
A dry type unit on a 480 V primary uses the same limits as a breaker, up to 300 amps for primary only protection. A 167 kVA pad mount on 12470 volts draws only 7.7 amps, so its fuse comes from the manufacturer coordination table, not from a percentage rule.
How many amps does a 167 kVA transformer draw?
201 amps at 480 V three phase, 464 amps at 208 V, 402 amps at 240 V and 161 amps at 600 V. Single phase it is 696 amps at 240 V.
What size breaker for a 167 kVA transformer 480 to 240 volts single phase?
A single phase 167 kVA transformer from 480 V to 240 V draws 348 amps on the 480 V primary, so a primary breaker of 450 amps is the usual size when only the primary is protected. The 240 V secondary carries 696 amps, with a largest secondary breaker of 1000 amps. Both use 125 percent of full load current, rounded up to the next standard size in NEC 240.6(A).
What is the primary and secondary current of a 167 kVA transformer?
For 480 to 208Y/120 volts, 201 amps on the primary and 464 amps on the secondary. The kVA is the same on both sides, the current scales inversely with voltage.
Sources, EC and M, NEC guidelines for transformer and transformer feeder protection, NEC Table 310.16 and Table 250.66 as printed on this site, current figures computed on this site. Padmount Supply LLC. Always confirm with the adopted NEC edition and the local inspector.