Home / Charts / How many acres does 1 MW of solar need

How many acres does 1 MW of solar need

Plan on 5 to 10 acres for each megawatt of AC output, and about 8 to 9 acres for a typical utility scale plant. NREL measured 7.6 acres per MWac for fixed tilt plants and 8.7 acres for single axis tracking. The table below turns that range into acres for 1 MW to 500 MW, with panel counts and the number of 2,500 kVA pad mounted step up transformers the output needs.

Updated November 16, 2026

Acres by project size

The acres columns multiply the project size in MWac by 5 acres, the low end of the NREL planning range, by 7.6 and 8.7, the NREL averages for fixed tilt and single axis tracking, and by 10, the high end. The panel columns divide the DC capacity by the module wattage, and the last column rounds up the number of 2,500 kVA transformers needed to carry the AC output at unity power factor.

Project sizeAcres at 5 per MWAcres fixed tilt, 7.6Acres tracking, 8.7Acres at 10 per MWPanels at 400 WPanels at 500 WPanels at 600 W2,500 kVA transformers
1 MW589102,5002,0001,6671
2 MW101517205,0004,0003,3331
5 MW2538445012,50010,0008,3332
10 MW50768710025,00020,00016,6674
20 MW10015217420050,00040,00033,3338
50 MW250380435500125,000100,00083,33320
100 MW5007608701,000250,000200,000166,66740
200 MW1,0001,5201,7402,000500,000400,000333,33380
500 MW2,5003,8004,3505,0001,250,0001,000,000833,333200

Computed. Panel counts assume DC capacity equal to the MW shown. Projects built with a DC to AC ratio above 1 carry more panels per MWac. Acreage is total site area, so fencing, roads and setbacks are included.

Fixed tilt compared with single axis tracking

NREL’s survey of built plants found fixed tilt systems used about 7.6 acres per MWac of total area and 5.5 acres of direct impact, while single axis tracking used about 8.7 acres of total area and 6.3 acres of direct impact. The capacity weighted average across all plants was 8.9 acres per MWac. A later NREL planning presentation puts the range at 5 to 10 acres per MW depending on tracking, site design and environmental constraints, and notes that most utility scale PV capacity added in 2019 used trackers, which need more land.

MWac and MWdc change the answer

Acres per MW depends on which megawatt you use. A plant with 1.3 MW of panels feeding 1 MW of inverters is a 1 MWac project, and the extra panels need land. Always check whether a quoted figure is per MWac or per MWdc before comparing sites.

What else takes land

Total area also covers access roads, the project substation or pad mounted step up transformers, setbacks and buffers, and any battery storage yard. Direct impact area is the part under panels, roads and equipment, and it is smaller than the fenced site.

  • Inverters and pad mounted step up transformers sit on pads along the array rows, one 2,500 kVA unit per roughly 2.5 MW block in the table above.
  • A project substation steps the collection voltage up to the utility line.
  • A battery storage yard adds its own pads and transformers.

Common questions

How many acres do you need for 1 MW of solar

About 5 to 10 acres per MWac. NREL measured 7.6 acres per MWac for fixed tilt and 8.7 acres for single axis tracking.

How many acres for a 100 MW solar farm

Roughly 500 to 1,000 acres, with 760 acres at the fixed tilt average and 870 acres at the tracking average.

How many acres for a 5 MW solar farm

About 25 to 50 acres, or 38 acres at the fixed tilt average of 7.6 acres per MWac.

How many solar panels are in 1 MW

At 500 W per module, 2,000 panels make 1 MW of DC capacity. At 400 W it is 2,500 and at 600 W it is 1,667.

Do trackers use more land

Yes. NREL found single axis tracking plants used about 8.7 acres per MWac against 7.6 for fixed tilt.

What transformer does a solar farm need

Each inverter block steps up to the collection voltage through a pad mounted transformer, often 2,500 kVA or larger, before a project substation steps up to the utility voltage.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.

More charts

Wire ampacity chart from NEC Table 310.16
NEC Table 310.16 ampacities for copper and aluminum at 60, 75 and 90°C from 14 AWG to 2000 kcmil, with the terminal rule, small conductor limits and derating factors.
NEMA enclosure ratings chart
What NEMA Types 1, 3R, 4, 4X, 12 and the rest protect against, side by side, with the IP codes three published charts give for each and why they disagree.
Motor full load amps chart
Three phase motor full load amps from 1/2 to 500 HP at 115, 200, 208, 230, 460, 575 and 2300 V from NEC Table 430.250, single phase from 430.248, with wire, breaker and kVA by HP.
What size wire for every amp rating, 15 to 4000 amps
Wire size by amps from 15 to 400 A in copper and aluminum, the dwelling service sizes under NEC 310.12, and parallel sets for 400 to 4000 A services, with a calculator.
Primary distribution voltages, 4.16 kV to 34.5 kV
Every standard US primary voltage from 2.4 kV to 69 kV with its phase to ground value, wye or delta, insulation class and BIL, and what 12470Y/7200 on a nameplate means.
Commercial electrical service sizes, amps, kVA and transformer
Standard commercial service sizes from 100 to 4000 amps at 208Y/120 and 480Y/277 volts, the kVA each one carries, the transformer that feeds it, and when ground fault protection applies.
Breaker size chart, every standard breaker rating and its wire size
Every standard breaker size in NEC 240.6(A) from 10 to 6000 amps, the matching copper and aluminum wire size at 60 and 75°C, the 125 percent continuous load rule and common appliance circuits.
Transformer fuse size chart, primary full load amps by kVA and voltage
Primary full load amps for 25 to 2500 kVA three phase transformers at 4.16 to 34.5 kV, the NEC 450.3(B) 125 and 250 percent limits worked out at 480 V, and how pad mount fuses are chosen.
Copper bus bar ampacity chart, by bar size and temperature rise
Ampacity of 68 standard rectangular copper bus bar sizes from 1/16 by 1/2 inch to 3/4 by 12 inch at 30, 50 and 65 C rise, with area, weight and how to pick a bar for a transformer secondary.
Electrical service size chart, how many kW is a 200 amp service
kVA and kW for 60 to 1200 amp electrical services on single phase 240 volt and three phase 208, 240 and 480 volt systems, with 80 percent loading columns and the formula behind every figure.
Grounding electrode conductor size chart from NEC Table 250.66
NEC Table 250.66 grounding electrode conductor sizes in copper and aluminum, the 6 AWG rod rule and 4 AWG concrete encased rule, and the ground wire size for 100, 200, 400, 600, 800 and 1200 amp services.
Generator kVA to kW and amps chart
Generator kVA to kW and full load amps for 10 to 3,000 kVA at 120/240, 208, 240, 480, 600, 2,400 and 4,160 volts, computed at 0.8 power factor, with kW to kVA at other power factors.
Service wire size chart
Service entrance wire size for 100, 125, 150, 200, 225, 320, 400 and larger services in copper and aluminum, with the NEC 310.12 dwelling rule, parallel sets to 2000 amps, ground wire and the transformer behind the service.
NEMA plug and receptacle chart
NEMA plug chart for every straight blade and locking configuration, with voltage, poles, wires, amp ratings, the 80 percent continuous limit, how to read a name like 14-50R and L6-30P and which series fits 120, 208, 240 and 480 volts.
AWG wire gauge chart with diameter, mm2, kcmil and resistance
American wire gauge chart from 4/0 to 40 AWG with diameter in inches and mm, area in mm2 and kcmil, and copper resistance, plus a kcmil to mm2 table from 250 to 2000 kcmil.
CallGet a quote