Home / Charts / Service wire size chart
Service wire size chart
A 200 amp dwelling service needs 2/0 copper or 4/0 aluminum. Any other 200 amp service needs 3/0 copper or 250 kcmil aluminum. The gap is the 83 percent rule in NEC 310.12, which lets a one family or multifamily dwelling service use smaller wire than the full ampacity table asks for. The chart below gives both answers for every size from 100 to 400 amps, then parallel sets up to 2000 amps, the ground wire and the transformer that has to carry the load.
Updated November 17, 2026
Service wire size by amps, dwelling and other buildings
The first two columns follow NEC Table 310.12, the dwelling service table, and read straight off the code. The last two columns are the smallest conductor whose 75 degree C ampacity in Table 310.16 is at least the service rating, which is the answer for a shop, a store, a barn or any other building that is not a dwelling. Use the 75 degree column because service equipment terminals are usually rated 75 degrees C.
| Service rating | Dwelling, copper | Dwelling, aluminum | Other building, copper | Other building, aluminum |
|---|---|---|---|---|
| 100 A | 4 AWG | 2 AWG | 3 AWG | 1 AWG |
| 110 A | 3 AWG | 1 AWG | 2 AWG | 1/0 AWG |
| 125 A | 2 AWG | 1/0 AWG | 1 AWG | 2/0 AWG |
| 150 A | 1 AWG | 2/0 AWG | 1/0 AWG | 3/0 AWG |
| 175 A | 1/0 AWG | 3/0 AWG | 2/0 AWG | 4/0 AWG |
| 200 A | 2/0 AWG | 4/0 AWG | 3/0 AWG | 250 kcmil |
| 225 A | 3/0 AWG | 250 kcmil | 4/0 AWG | 300 kcmil |
| 250 A | 4/0 AWG | 300 kcmil | 250 kcmil | 350 kcmil |
| 300 A | 250 kcmil | 350 kcmil | 350 kcmil | 500 kcmil |
| 350 A | 350 kcmil | 500 kcmil | 500 kcmil | 700 kcmil |
| 400 A | 400 kcmil | 600 kcmil | 600 kcmil | 900 kcmil |
Dwelling columns from NEC Table 310.12 as published by Learn Metrics. Other building columns are computed from the 75 degree C ampacities in the wire ampacity chart on this site. Aluminum means aluminum or copper clad aluminum.
How the 83 percent rule works
NEC 310.12 lets the conductors of a dwelling service carry as little as 83 percent of the service rating. A 200 amp service can use wire good for 166 amps, and 2/0 copper at 175 amps clears that. Without the rule the same service needs wire good for 200 amps, which is 3/0 copper. The table shows the margin for each size, the minimum ampacity at 83 percent, then the dwelling conductor and its Table 310.16 ampacity at 75 degrees C.
| Service rating | Minimum ampacity at 83 percent | Copper chosen and its ampacity | Aluminum chosen and its ampacity |
|---|---|---|---|
| 100 A | 83.0 A | 4 AWG, 85 A | 2 AWG, 90 A |
| 110 A | 91.3 A | 3 AWG, 100 A | 1 AWG, 100 A |
| 125 A | 103.8 A | 2 AWG, 115 A | 1/0 AWG, 120 A |
| 150 A | 124.5 A | 1 AWG, 130 A | 2/0 AWG, 135 A |
| 175 A | 145.2 A | 1/0 AWG, 150 A | 3/0 AWG, 155 A |
| 200 A | 166.0 A | 2/0 AWG, 175 A | 4/0 AWG, 180 A |
| 225 A | 186.8 A | 3/0 AWG, 200 A | 250 kcmil, 205 A |
| 250 A | 207.5 A | 4/0 AWG, 230 A | 300 kcmil, 230 A |
| 300 A | 249.0 A | 250 kcmil, 255 A | 350 kcmil, 250 A |
| 350 A | 290.5 A | 350 kcmil, 310 A | 500 kcmil, 310 A |
| 400 A | 332.0 A | 400 kcmil, 335 A | 600 kcmil, 340 A |
When the 83 percent rule does not apply
The rule is for the service or feeder that carries the whole load of a one family dwelling, a two family dwelling or a multifamily dwelling, and the table covers single phase services from 100 to 400 amps. The conductors have to be rated 75 degrees C or higher. A shop, a barn, a commercial building or a feeder to a subpanel that does not carry the whole load of the dwelling is sized from the full ampacity table, which is why the other building columns above are larger. Corrections for heat and for more than three current carrying conductors in a raceway can still change the answer, so the inspector and the code edition in force decide.
- Dwelling service from 100 to 400 amps, single phase, 75 degrees C or higher wire, use NEC 310.12.
- Any other building, or a three phase service, size from Table 310.16 at the service rating.
- Above 400 amps, run parallel sets, see the next table.
Services over 400 amps, parallel sets
Large services are built from sets of smaller conductors in parallel. The table picks the fewest sets that keep every conductor at 600 kcmil or smaller in copper, or 900 kcmil in aluminum, using the 75 degree C ampacities. That cap is a practical choice and not a code limit. Every set in a parallel run has to be the same size, length and material.
| Service rating | Copper, 75 degrees C | Aluminum, 75 degrees C |
|---|---|---|
| 500 A | 2 sets of 250 kcmil, 510 A | 2 sets of 350 kcmil, 500 A |
| 600 A | 2 sets of 350 kcmil, 620 A | 2 sets of 500 kcmil, 620 A |
| 800 A | 2 sets of 600 kcmil, 840 A | 2 sets of 900 kcmil, 850 A |
| 1000 A | 3 sets of 400 kcmil, 1,005 A | 3 sets of 600 kcmil, 1,020 A |
| 1200 A | 3 sets of 600 kcmil, 1,260 A | 3 sets of 900 kcmil, 1,275 A |
| 1600 A | 4 sets of 600 kcmil, 1,680 A | 4 sets of 900 kcmil, 1,700 A |
| 2000 A | 5 sets of 600 kcmil, 2,100 A | 5 sets of 900 kcmil, 2,125 A |
Computed from NEC Table 310.16 as shown in the wire ampacity chart on this site. These are services sized at 100 percent of the rating. Check the inspector for the 83 percent rule on dwellings.
Ground wire for each service size
The grounding electrode conductor comes from NEC Table 250.66 and depends on the size of the service conductors, not the amp rating. The table gives the copper ground wire for the dwelling conductors above, in copper and in aluminum. A ground rod alone never needs more than 6 AWG copper, and a concrete encased electrode never more than 4 AWG copper, so the ground wire can be smaller than the table. The full table and the caps are in the grounding electrode conductor size chart.
| Service rating | Service wire, copper | Ground wire for copper service wire | Service wire, aluminum | Ground wire for aluminum service wire |
|---|---|---|---|---|
| 100 A | 4 AWG | 8 AWG | 2 AWG | 8 AWG |
| 125 A | 2 AWG | 8 AWG | 1/0 AWG | 8 AWG |
| 150 A | 1 AWG | 6 AWG | 2/0 AWG | 6 AWG |
| 200 A | 2/0 AWG | 4 AWG | 4/0 AWG | 4 AWG |
| 300 A | 250 kcmil | 2 AWG | 350 kcmil | 2 AWG |
| 400 A | 400 kcmil | 1/0 AWG | 600 kcmil | 1/0 AWG |
What size transformer sits behind the service
The utility sizes its transformer from the demand of the building, not from the service rating. The table shows the ceiling, the kVA a single phase 240 volt service could carry at full rating and the next standard single phase pad mounted transformer size above it. Larger commercial services are three phase and are sized with the kVA to amps calculator.
| Service rating | kVA at 240 V single phase | Next standard single phase pad mount |
|---|---|---|
| 100 A | 24.0 | 25 kVA |
| 150 A | 36.0 | 50 kVA |
| 200 A | 48.0 | 50 kVA |
| 320 A | 76.8 | 100 kVA |
| 400 A | 96.0 | 100 kVA |
Long runs and voltage drop
The chart sizes wire for heat. A long run from the meter to the panel, or from a pad mounted transformer to a distant building, also loses voltage, and the wire may have to go up a size or two to hold the drop to an acceptable figure. Use the voltage drop calculator for the run length and load. It is not covered by the tables on this page.
Common questions
What size wire for a 200 amp service
For a dwelling, 2/0 copper or 4/0 aluminum under NEC 310.12, because the rule lets the wire carry 83 percent of 200 amps, or 166 amps, and 2/0 copper is good for 175 amps. For any other building, 3/0 copper at 200 amps or 250 kcmil aluminum at 205 amps.
What size wire for a 100 amp service
For a dwelling, 4 AWG copper or 2 AWG aluminum. For any other building, 3 AWG copper at 100 amps or 1 AWG aluminum at 100 amps.
What size wire for a 400 amp service
For a dwelling, 400 kcmil copper or 600 kcmil aluminum. For any other building, 600 kcmil copper at 420 amps, or two sets of 3/0 copper in parallel, which carry 400 amps together, as the practical alternative.
What size wire for a 150 amp service
For a dwelling, 1 AWG copper or 2/0 AWG aluminum. For any other building, 1/0 copper at 150 amps or 3/0 aluminum at 155 amps.
What is the 83 percent rule
NEC 310.12 lets service and feeder conductors for a dwelling have an ampacity of at least 83 percent of the service rating. It applies to one family, two family and multifamily dwellings, from 100 to 400 amps, with wire rated at 75 degrees C or higher.
Is aluminum service wire allowed
Yes. Aluminum needs a larger conductor for the same ampacity, usually two sizes larger. At 200 amps for a dwelling the code lists 2/0 copper or 4/0 aluminum. Use terminals and connectors listed for aluminum.
What size ground wire for a 200 amp service
With 2/0 copper service conductors, or 4/0 aluminum conductors, the copper grounding electrode conductor is 4 AWG under Table 250.66. A connection to a ground rod alone never needs more than 6 AWG copper.
Related pages
Sources
- Learn Metrics, NEC 310.12 table, wire sizes for 100 to 400 amp services
- NFPA, considerations for single family residential electrical services based on the 2020 NEC
- EC&M, using 310.12 to size service and feeder conductors
- Mike Holt, 2020 Table 310.12 for dwelling services and feeders
Free to cite with a link to this page. Always check the edition of the code your inspector enforces.