Padmount Supply

Home / Charts / Service wire size chart

Service wire size chart

A 200 amp dwelling service needs 2/0 copper or 4/0 aluminum. Any other 200 amp service needs 3/0 copper or 250 kcmil aluminum. The gap is the 83 percent rule in NEC 310.12, which lets a one family or multifamily dwelling service use smaller wire than the full ampacity table asks for. The chart below gives both answers for every size from 100 to 400 amps, then parallel sets up to 2000 amps, the ground wire and the transformer that has to carry the load.

Updated November 17, 2026

Service wire size by amps, dwelling and other buildings

The first two columns follow NEC Table 310.12, the dwelling service table, and read straight off the code. The last two columns are the smallest conductor whose 75 degree C ampacity in Table 310.16 is at least the service rating, which is the answer for a shop, a store, a barn or any other building that is not a dwelling. Use the 75 degree column because service equipment terminals are usually rated 75 degrees C.

Service ratingDwelling, copperDwelling, aluminumOther building, copperOther building, aluminum
100 A4 AWG2 AWG3 AWG1 AWG
110 A3 AWG1 AWG2 AWG1/0 AWG
125 A2 AWG1/0 AWG1 AWG2/0 AWG
150 A1 AWG2/0 AWG1/0 AWG3/0 AWG
175 A1/0 AWG3/0 AWG2/0 AWG4/0 AWG
200 A2/0 AWG4/0 AWG3/0 AWG250 kcmil
225 A3/0 AWG250 kcmil4/0 AWG300 kcmil
250 A4/0 AWG300 kcmil250 kcmil350 kcmil
300 A250 kcmil350 kcmil350 kcmil500 kcmil
350 A350 kcmil500 kcmil500 kcmil700 kcmil
400 A400 kcmil600 kcmil600 kcmil900 kcmil

Dwelling columns from NEC Table 310.12 as published by Learn Metrics. Other building columns are computed from the 75 degree C ampacities in the wire ampacity chart on this site. Aluminum means aluminum or copper clad aluminum.

How the 83 percent rule works

NEC 310.12 lets the conductors of a dwelling service carry as little as 83 percent of the service rating. A 200 amp service can use wire good for 166 amps, and 2/0 copper at 175 amps clears that. Without the rule the same service needs wire good for 200 amps, which is 3/0 copper. The table shows the margin for each size, the minimum ampacity at 83 percent, then the dwelling conductor and its Table 310.16 ampacity at 75 degrees C.

Service ratingMinimum ampacity at 83 percentCopper chosen and its ampacityAluminum chosen and its ampacity
100 A83.0 A4 AWG, 85 A2 AWG, 90 A
110 A91.3 A3 AWG, 100 A1 AWG, 100 A
125 A103.8 A2 AWG, 115 A1/0 AWG, 120 A
150 A124.5 A1 AWG, 130 A2/0 AWG, 135 A
175 A145.2 A1/0 AWG, 150 A3/0 AWG, 155 A
200 A166.0 A2/0 AWG, 175 A4/0 AWG, 180 A
225 A186.8 A3/0 AWG, 200 A250 kcmil, 205 A
250 A207.5 A4/0 AWG, 230 A300 kcmil, 230 A
300 A249.0 A250 kcmil, 255 A350 kcmil, 250 A
350 A290.5 A350 kcmil, 310 A500 kcmil, 310 A
400 A332.0 A400 kcmil, 335 A600 kcmil, 340 A

When the 83 percent rule does not apply

The rule is for the service or feeder that carries the whole load of a one family dwelling, a two family dwelling or a multifamily dwelling, and the table covers single phase services from 100 to 400 amps. The conductors have to be rated 75 degrees C or higher. A shop, a barn, a commercial building or a feeder to a subpanel that does not carry the whole load of the dwelling is sized from the full ampacity table, which is why the other building columns above are larger. Corrections for heat and for more than three current carrying conductors in a raceway can still change the answer, so the inspector and the code edition in force decide.

  • Dwelling service from 100 to 400 amps, single phase, 75 degrees C or higher wire, use NEC 310.12.
  • Any other building, or a three phase service, size from Table 310.16 at the service rating.
  • Above 400 amps, run parallel sets, see the next table.

Services over 400 amps, parallel sets

Large services are built from sets of smaller conductors in parallel. The table picks the fewest sets that keep every conductor at 600 kcmil or smaller in copper, or 900 kcmil in aluminum, using the 75 degree C ampacities. That cap is a practical choice and not a code limit. Every set in a parallel run has to be the same size, length and material.

Service ratingCopper, 75 degrees CAluminum, 75 degrees C
500 A2 sets of 250 kcmil, 510 A2 sets of 350 kcmil, 500 A
600 A2 sets of 350 kcmil, 620 A2 sets of 500 kcmil, 620 A
800 A2 sets of 600 kcmil, 840 A2 sets of 900 kcmil, 850 A
1000 A3 sets of 400 kcmil, 1,005 A3 sets of 600 kcmil, 1,020 A
1200 A3 sets of 600 kcmil, 1,260 A3 sets of 900 kcmil, 1,275 A
1600 A4 sets of 600 kcmil, 1,680 A4 sets of 900 kcmil, 1,700 A
2000 A5 sets of 600 kcmil, 2,100 A5 sets of 900 kcmil, 2,125 A

Computed from NEC Table 310.16 as shown in the wire ampacity chart on this site. These are services sized at 100 percent of the rating. Check the inspector for the 83 percent rule on dwellings.

Ground wire for each service size

The grounding electrode conductor comes from NEC Table 250.66 and depends on the size of the service conductors, not the amp rating. The table gives the copper ground wire for the dwelling conductors above, in copper and in aluminum. A ground rod alone never needs more than 6 AWG copper, and a concrete encased electrode never more than 4 AWG copper, so the ground wire can be smaller than the table. The full table and the caps are in the grounding electrode conductor size chart.

Service ratingService wire, copperGround wire for copper service wireService wire, aluminumGround wire for aluminum service wire
100 A4 AWG8 AWG2 AWG8 AWG
125 A2 AWG8 AWG1/0 AWG8 AWG
150 A1 AWG6 AWG2/0 AWG6 AWG
200 A2/0 AWG4 AWG4/0 AWG4 AWG
300 A250 kcmil2 AWG350 kcmil2 AWG
400 A400 kcmil1/0 AWG600 kcmil1/0 AWG

What size transformer sits behind the service

The utility sizes its transformer from the demand of the building, not from the service rating. The table shows the ceiling, the kVA a single phase 240 volt service could carry at full rating and the next standard single phase pad mounted transformer size above it. Larger commercial services are three phase and are sized with the kVA to amps calculator.

Service ratingkVA at 240 V single phaseNext standard single phase pad mount
100 A24.025 kVA
150 A36.050 kVA
200 A48.050 kVA
320 A76.8100 kVA
400 A96.0100 kVA

Long runs and voltage drop

The chart sizes wire for heat. A long run from the meter to the panel, or from a pad mounted transformer to a distant building, also loses voltage, and the wire may have to go up a size or two to hold the drop to an acceptable figure. Use the voltage drop calculator for the run length and load. It is not covered by the tables on this page.

Common questions

What size wire for a 200 amp service

For a dwelling, 2/0 copper or 4/0 aluminum under NEC 310.12, because the rule lets the wire carry 83 percent of 200 amps, or 166 amps, and 2/0 copper is good for 175 amps. For any other building, 3/0 copper at 200 amps or 250 kcmil aluminum at 205 amps.

What size wire for a 100 amp service

For a dwelling, 4 AWG copper or 2 AWG aluminum. For any other building, 3 AWG copper at 100 amps or 1 AWG aluminum at 100 amps.

What size wire for a 400 amp service

For a dwelling, 400 kcmil copper or 600 kcmil aluminum. For any other building, 600 kcmil copper at 420 amps, or two sets of 3/0 copper in parallel, which carry 400 amps together, as the practical alternative.

What size wire for a 150 amp service

For a dwelling, 1 AWG copper or 2/0 AWG aluminum. For any other building, 1/0 copper at 150 amps or 3/0 aluminum at 155 amps.

What is the 83 percent rule

NEC 310.12 lets service and feeder conductors for a dwelling have an ampacity of at least 83 percent of the service rating. It applies to one family, two family and multifamily dwellings, from 100 to 400 amps, with wire rated at 75 degrees C or higher.

Is aluminum service wire allowed

Yes. Aluminum needs a larger conductor for the same ampacity, usually two sizes larger. At 200 amps for a dwelling the code lists 2/0 copper or 4/0 aluminum. Use terminals and connectors listed for aluminum.

What size ground wire for a 200 amp service

With 2/0 copper service conductors, or 4/0 aluminum conductors, the copper grounding electrode conductor is 4 AWG under Table 250.66. A connection to a ground rod alone never needs more than 6 AWG copper.

Related pages

Sources

Free to cite with a link to this page. Always check the edition of the code your inspector enforces.

More charts

Wire ampacity chart from NEC Table 310.16
NEC Table 310.16 ampacities for copper and aluminum at 60, 75 and 90°C from 14 AWG to 2000 kcmil, with the terminal rule, small conductor limits and derating factors.
NEMA enclosure ratings chart
What NEMA Types 1, 3R, 4, 4X, 12 and the rest protect against, side by side, with the IP codes three published charts give for each and why they disagree.
Motor full load amps chart
Three phase motor full load amps from 1/2 to 500 HP at 115, 200, 208, 230, 460, 575 and 2300 V from NEC Table 430.250, single phase from 430.248, with wire, breaker and kVA by HP.
What size wire for every amp rating, 15 to 4000 amps
Wire size by amps from 15 to 400 A in copper and aluminum, the dwelling service sizes under NEC 310.12, and parallel sets for 400 to 4000 A services, with a calculator.
Primary distribution voltages, 4.16 kV to 34.5 kV
Every standard US primary voltage from 2.4 kV to 69 kV with its phase to ground value, wye or delta, insulation class and BIL, and what 12470Y/7200 on a nameplate means.
Commercial electrical service sizes, amps, kVA and transformer
Standard commercial service sizes from 100 to 4000 amps at 208Y/120 and 480Y/277 volts, the kVA each one carries, the transformer that feeds it, and when ground fault protection applies.
Breaker size chart, every standard breaker rating and its wire size
Every standard breaker size in NEC 240.6(A) from 10 to 6000 amps, the matching copper and aluminum wire size at 60 and 75°C, the 125 percent continuous load rule and common appliance circuits.
Transformer fuse size chart, primary full load amps by kVA and voltage
Primary full load amps for 25 to 2500 kVA three phase transformers at 4.16 to 34.5 kV, the NEC 450.3(B) 125 and 250 percent limits worked out at 480 V, and how pad mount fuses are chosen.
Copper bus bar ampacity chart, by bar size and temperature rise
Ampacity of 68 standard rectangular copper bus bar sizes from 1/16 by 1/2 inch to 3/4 by 12 inch at 30, 50 and 65 C rise, with area, weight and how to pick a bar for a transformer secondary.
Electrical service size chart, how many kW is a 200 amp service
kVA and kW for 60 to 1200 amp electrical services on single phase 240 volt and three phase 208, 240 and 480 volt systems, with 80 percent loading columns and the formula behind every figure.
Grounding electrode conductor size chart from NEC Table 250.66
NEC Table 250.66 grounding electrode conductor sizes in copper and aluminum, the 6 AWG rod rule and 4 AWG concrete encased rule, and the ground wire size for 100, 200, 400, 600, 800 and 1200 amp services.
How many acres does 1 MW of solar need
A utility scale solar farm needs about 5 to 10 acres per MWac. Fixed tilt averages 7.6 acres and single axis tracking 8.7 acres, with a table from 1 to 500 MW, panel counts and step up transformers.
Generator kVA to kW and amps chart
Generator kVA to kW and full load amps for 10 to 3,000 kVA at 120/240, 208, 240, 480, 600, 2,400 and 4,160 volts, computed at 0.8 power factor, with kW to kVA at other power factors.
NEMA plug and receptacle chart
NEMA plug chart for every straight blade and locking configuration, with voltage, poles, wires, amp ratings, the 80 percent continuous limit, how to read a name like 14-50R and L6-30P and which series fits 120, 208, 240 and 480 volts.
AWG wire gauge chart with diameter, mm2, kcmil and resistance
American wire gauge chart from 4/0 to 40 AWG with diameter in inches and mm, area in mm2 and kcmil, and copper resistance, plus a kcmil to mm2 table from 250 to 2000 kcmil.
CallGet a quote